14
Service
Device replacement
Manual – PROFINET IO Interfaces, Field Distributors
170
14.1.2
Error list for fieldbus interfaces
Code Meaning
Response
Possible cause
Measure
25
EEPROM
Rapid stop of
MOVIMOT
®
drives
DO = 0
Error while accessing
EEPROM
•
Call up the factory setting
"Delivery state", perform a
reset and set parameters
again (Caution: The IPOS
program will be deleted).
•
If the problem occurs again,
contact SEW‑EURODRIVE
Service.
28
Fieldbus
timeout
Process output
data = 0
DO = 0
(can be switched
off)
No communication between
master and slave within the
configured response monitor-
ing.
•
Check master communica-
tion routine.
37
Watchdog
error
Communication to
MOVIMOT
®
stopped
DO = 0
Error while executing system
software
•
Contact SEW‑EURODRIVE
Service.
28
Software
error
45
Initialization
fault
Error after self-test during re-
set
•
Perform a reset. If the prob-
lem occurs again, contact
SEW‑EURODRIVE-Service.
97
Copy data
Error while copying data re-
cord.
Data is not consistent.
•
Try to copy the data again;
reset the device to the fact-
ory setting "Delivery state"
first.
111
MOVIMOT
®
Timeout
No response
One or several stations
(MOVIMOT
®
) could not be ad-
dressed by the MQ.. within the
timeout interval.
•
Check voltage supply and
RS485 wiring.
•
Check address of con-
figured nodes.
112
Periphery
error
e.g. overload of a digital out-
put
•
Analyze MFE status word
and correct cause of error.
14.2
Device replacement
14.2.1
Notes on replacing devices
The MFE fieldbus interface allows for a quick device replacement. The MFE fieldbus
interface is equipped with a replaceable memory card on which all Ethernet paramet-
ers are automatically stored.
If the MFE fieldbus interface has to be replaced, the plant can be started up again
quickly by simply re-plugging the memory card.
22870857/EN – 12/2016