3
Safety-related conditions
Startup requirements
Manual – Functional Safety
15
3.3.1
Sample circuit "safety relay"
The following figure shows the disconnection of an external safety relay.
[4]
[3]
[1]
[5]
[6]
[2] U
18014400103440907
[1]
Safety relay with approval
[2]
DC 24 V voltage supply
[3]
Fuses in accordance with the manufacturer's specifications of the safety relay
[4]
Safety-related DC 24 V voltage supply
[5]
Reset button for manual reset
[6]
Approved emergency stop actuating device
3.4
Startup requirements
After parameterization and startup, the system startup engineer has to check and doc-
ument the correct performance of the safety functions.
For MOVIFIT
®
applications with safety-related disconnection of the drive
•
In stop category 0 or 1 in accordance with EN 60204-1
•
Restart inhibit in accordance with EN ISO 14118
•
In compliance with performance level d according to EN ISO 13849-1
you must, as a general rule, carry out and document startup checks of the disconnect-
ing device and the correct wiring.
During startup you must include signal detection of the safety-related control voltage in
the function test.
29157056/EN – 09/2019