4 mm laboratory safety plug connectors with rigid insulating sleeve, suited for nom-
inal voltages of up to 1000 V.
•
Didactics connection cable from SEW‑EURODRIVE.
The cable must not be longer than 3 m.
4.1.4
PE line connection according to EN 61800‑5‑1
Earth-leakage currents of ≥ 3.5 mA can occur during normal operation. Observe the
following for reliable PE connection:
•
Supply system cable < 10 mm
2
:
– Second PE conductor with the same cross section as the supply system cable
routed parallel to the protective earth via separate terminals, or
– Copper PE conductor with a cross section of 10 mm
2
•
Supply system cable 10 to 16 mm
2
:
– Copper protective earth conductor with the same cross section as the supply
system cable.
•
Supply system cable 16 to 35 mm
2
:
– Copper PE conductor with a cross section of 16 mm
2
•
Supply system cable > 35 mm
2
:
– Copper PE conductor with half the cross section of the supply system cable.
4.1.5
Interference emission
Recommendation: Use shielded motor cables for EMC compliant installation.
4.2
Electrical connections
4.2.1
Power section connection
N
230V / 50-60 Hz
L
X1
[1]
[2]
15172091659
[1]
L: Line connection phase
[2]
N: Line connection of neutral conductor