Installation Guide
“Multi-Sense” Model 260 Series
Multi-Range Differential Pressure Transducer
GENERAL INFORMATION
Every Model 260 has been calibrated and tested before shipment to guarantee
performance for all pressure ranges.
The Model 260 is available in four versions, which have field selectable range
capability via a slide switch. See four versions below:
MULTI-SENSE RANGE SPECIFICATIONS
The Model 260 is available in three field selectable output configurations. See three
versions below
:
SIMPLE 5-STEP SETUP INSTRUCTIONS - STEPS 2 - 5
Power On - LCD Display
Display momentarily toggles thru all existing setup parameters on initial power
up. Pressure is normally indicated on display. Units are either in inches of water
column (WC) MS1 & MS2, or Pascal (Pa) MS3 & MS4.
Multi-Sense Voltage
3-Wire, 0-5, 0-10 VDC Configuration
Model 260
Multi-Sense Current
2-Wire, 4-20 mA Configuration
STEP 1: Wire and Power Up Unit -
Follow diagrams
below for 2-wire and 3-wire configurations. After
completing wiring requirements - Apply power to
the Model 260.
SIMPLE 5-STEP SETUP INSTRUCTIONS -
STEP 1
For CE compliance a properly grounded shielding cable is
required.
ELECTRICAL CONNECTIONS
-
EXC
COM
OUT
Power
Supply
13 - 30V
-
24V AC/DC
Nominal
Excitation
-
Model C260
+
-
EXC
COM
OUT
+
-
24V (DC Only)
Nominal
Excitation
+
-
X
Typical 250 Ohm
Sense Resistor
for 1-5V Output
Measurement
Voltage
Monitor
Power
Supply
13 - 30V
Current
Monitor
Removable Terminal Block for Easy Wiring
MECHANICAL INSTALLATION
Mounting Position
Mount and calibrate in vertical position for quick and easy installa-
tion on ducts, walls or ceilings and in control rooms.
Media Compatibility
Model 260 transducers are designed to be used with air or
nonconducting gases.
Use with liquids or corrosive gases will damage the unit.
Environment
The operating temperature limits of the 260 are as follows:
Operating Temperature 32°F to 122°F (0°C to 50°C)
Compensated Temperature Range 32°F to 122°F (0°C to 50°C)
Model MS1 0.1”, 0.25”, 0.5” and 1.0” W.C. FS +/- 0.1”, 0.25”, 0.5” and 1.0” W.C. FS
Model MS2 1.0”, 2.5”, 5.0” and 10” W.C. FS +/- 1.0”, 2.5”, 5.0” and 10” W.C. FS
Model MS3 25, 50, 100 and 250 Pa FS +/- 25, 50, 100 and 250 Pa FS
Model MS4 .25, .50, 1.00 and 2.5 kPa +/- .25, .50, 1.00 and 2.5 kPa
Ranges
Version Unidirectional Bidirectional
2-Wire 4-20 mA (Current)
3-Wire 0-5, or 0-10 VDC (Voltage)
+
+
+
+
+
RANGE:
1 0.5 0.25 0.1
UNI/BI
ZERO
mA/Volt
+ -
2601MS1
S/N:
EXC
COM
OUT
*STEP 2: Select Pressure Range
:
Set
appropriate full scale range using
the Slide Switch Multiplier. LCD
will momentarily indicate selected
range.
STEP 5: Push Button
Zero
-
While at
zero pressure
Press and hold
the
Zero Push
Button
for 5
seconds to auto-
matically reset
output to zero.
STEP 3
:
Select Unidirectional
or Bi-directional mode.
**STEP 4:
Select Current (mA)
or Voltage 0-5, or
0-10 VDC output range.
*Step 2 will follow same
instructions for other inches of
water column and pascal
ranges.
* * Step 4 be sure to set mA/volt
switch to volt position if using
0 to 5 or 0 to 10V outputs
5V/10V
JUMPER
ZERO AND SPAN ADjUSTMENT*
The unit may be recalibrated in the field using the push button zero/span.
Zero Adjustment:
1. With unit at zero differential pressure, push zero button for 5 seconds. Units
output and display will update.
Span Adjustment:
2. Apply full scale pressure (Note: Full scale value of largest range.). Press and hold
zero button for 5 seconds. Units output and display will update.
*Zero and Span points must be within 10% of factory setting.
JUMPER
● ● ●
Date Code
● ● ●