MODEL: MRP6

•Terminal box
 Wiring conduit: G 1/2 female (two)
 Terminal screws: M3 pillar terminal
   (Sequential control signal suffix code B)
   M3 chromated steel
   (other terminal box types)
   (torque 0.5 N·m)
Housing material: Diecast aluminium
Drive: Stepping motor
Position detection: Potentiometer
Deadband: 0.1 – 4.5 % adjustable (factory set to 1.5 %)
Restarting timer: 0 – 10 sec. adjustable
(factory set to 1.5 sec.)
Isolation: AC power to signal
Zero adjustment: 0 – 25 %
Span adjustment: 50 - 100 %
Protective functions: Overload protection
Power indicator: Green LED turns on with power supplied.
Input indicator: Green LED turns on with normal input
Status indicator LED: Red light blinks in 2 sec. intervals in
normal operations; blinks in 0.5 sec. intervals when a
foreign object is detected mechanically caught inside.
Manual operation: Available

INPUT SPECIFICATIONS

■ DC Current: Input resistor incorporated (250 Ω)
■ DC Voltage: 1 – 5 V DC or specific range within 0 – 5 V
DC, minimum span 1 V
(For a current input, convert the current to a voltage with
250 Ω)
Input resistance: Approx. 1 MΩ
■ Forced open/close signal:
Dry contact inputs to command clockwise and
counterclockwise turns
Rating: 5 V DC @ 2.5 mA

OUTPUT SPECIFICATIONS

■ Operation Time & Torque (at rated power voltage)
MRP6-x3: 4 seconds / 90° 10 N·m (7.38 ft·lbs)
MRP6-x4: 7 seconds / 90° 16 N·m (11.8 ft·lbs)
MRP6-x6: 13 seconds / 90° 33 N·m (24.3 ft·lbs)
■ DC Voltage: 1 – 5 V DC (not isolated)
With “direct” action, 5 – 1 V DC position output is provided
proportionally to 4 – 20 mA DC (1 – 5 V DC) input.
Load resistance: ≥ 5 kΩ
■ Full-open / -closed signals: Limit switch contact
Rating: 125 V AC @ 0.75 A (cos ø = 1)
30 V DC @ 0.6 A (resistive load)
Mechanical life: 3 × 10

7

 cycles

Maximum operation frequency: 60 cycles/min.

INSTALLATION

Power consumption
•AC: Approx. 25 VA
•DC: Approx. 0.6 A
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 85 %RH (non-condensing)
Vibration: 0.5 G max.
Mounting position: All directions
Do not mount the actuator with its output stem or cable
connector on the upside if the actuator is to be exposed to
dripping water.
Weight
  DC powered: 2.7 kg (5.96 lbs)
  AC powered: 2.8 kg (6.17 lbs)
  Add 0.7 kg (1.54 lbs) for the terminal box.

PERFORMANCE

Resolution: 1/1000 or 0.09°, whichever is greater, with 0.1
% deadband setting
Insulation resistance
•AC powered: ≥ 100 MΩ with 500 V DC
(signal or metallic housing to power)
≥ 100 MΩ with 100 V DC
(signal to metallic housing)
•DC powered: ≥ 100 MΩ with 100 V DC
(signal or power to metallic housing)
Dielectric strength
•AC powered: 1500 V AC @ 1 minute
(signal or metallic housing to power)
100 V AC @ 1 minute
(signal to metallic housing)
•DC powered: 100 V AC @ 1 minute
(signal or power to metallic housing)

STANDARDS & APPROVALS

CE conformity:
EMC Directive (2004/108/EC)
  EMI EN 61000-6-4: 2007
  EMS EN 61000-6-2: 2005
Low Voltage Directive (2006/95/EC)
 EN 61010-1: 2001
 Measurement Category II
 Pollution Degree 2
 Full-open/-closed signal to other, power or metallic
 housing: Reinforced insulation (125 V)

TERMINOLOGY

• Overload (Lock) Protection
The Mini-Top Series is equipped with a protection circuit
against overload caused by for example the valve catching
an alien substance.

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for M-SYSTEM DANAGE

Page 1: ...h 0 Without 5 INPUT Current A 4 20 mA DC Input resistance 250 Ω Z Specify current See INPUT SPECIFICATIONS Voltage 6 1 5 V DC Input resistance approx 1 MΩ 0 Specify voltage See INPUT SPECIFICATIONS 6 CE MARKING C With 0 Without 7 POWER INPUT AC Power K3 100 120 V AC Operational voltage range 90 132 V 47 66 Hz Not selectable for CE L3 200 240 V AC Operational voltage range 180 264 V 47 66 Hz Not se...

Page 2: ...sed signals Limit switch contact Rating 125 V AC 0 75 A cos ø 1 30 V DC 0 6 A resistive load Mechanical life 3 10 7 cycles Maximum operation frequency 60 cycles min INSTALLATION Power consumption AC Approx 25 VA DC Approx 0 6 A Operating temperature 5 to 55 C 23 to 131 F Operating humidity 30 to 85 RH non condensing Vibration 0 5 G max Mounting position All directions Do not mount the actuator wit...

Page 3: ...or above 100 Limiters are set at approx 0 5 for the full closed side approx 100 5 for the full open side TERMINAL CONNECTIONS black 1 U V COM1 COM2 white 2 red 3 green 4 yellow 5 blue 6 gray 7 brown 8 1 to 8 Terminal No of terminal box Full open closed signals and forced open close signals are optional POWER INPUT POSITION OUTPUT 1 5V DC FULL OPEN or FULL CLOSED SIGNAL output stem turned CCW outpu...

Page 4: ...15 59 dia 22 87 67 2 64 12 0 043 sq 70 2 76 dia 0 MANUAL HANDLE STEM 6 24 sq 2 G 1 2 CONDUIT 4 M6 12 47 deep 90 deg pitch YOKE CONNECTION 110 4 33 136 5 35 199 7 83 16 63 YOKE SURFACE 35 1 38 60 2 36 7 5 30 23 91 34 134 20 79 32 5 1 28 Cable connector or leadwires not provided with terminal box TERMINAL BOX TYPE Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox se...

Page 5: ...COM2 CCW CW FULL OPEN or FULL CLOSED SIGNAL POSITION OUTPUT 1 5V DC POWER MODE SELECTOR POWER INPUT STATUS POT MOTOR LIMIT SW Full open closed signals and forced open close signals are optional Disregard the switching regulator circuit for DC power input Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic...

Page 6: ...eters 6 inches above the cover OUTDOOR USE When installing the MRP outdoor or where it is exposed to rain or water drops be sure to fasten the cable connector tightly and leave a slack of the cable Do not mount the MRP in such direction that the output stem or cable connector is at the top of the MRP unit ELECTRICAL CONNECTION With DC power type unit power supply and signal lines are not isolated ...

Page 7: ... life of the actuator FUSE A fuse is equipped for protection against overload current When you turn the power supply on check that the power LED is on If it is off check that the fuse is melted Replace it with a new one If the new fuse is melted again soon after it has been re placed there may be problems with the control PCB or the motor Contact M System or sales representative RE STARTING TIMER ...

Page 8: ...erse Actions Operation at Abnormally Low Input Power Indicator green with power supplied Input Indicator green with input applied Status Indicator red blinks in 2 sec intervals blinks in 0 5 sec intervals with mechanical lock detected Remark Turning adjustment potentiom eters and switches with a torque exceed ing their tolerance may destroy their stop pers Turn them carefully and stop where they h...

Page 9: ...EL MIN SPAN MAX SPAN MRP4 1 MRP5 1 45 90 MRP6 1 MRP4 2 90 180 MRP6 2 Standard Zero Position M i n i m u m s p a n M a x i m u m s p a n M a x i m u m O p e r a t i o n R a n g e 5 d e g 5 d e g Adjustable Zero Range Adjustable Span Range Figure 5 Minimum Maximum Span MRPx Bolts M5 Output Stem Coupling Yoke Valve Bonnet Figure 6 Example of the MRP Mounted to a Valve 1 Supply power to the MRP and ap...

Page 10: ...gnal COM2 COM1 COM2 POWER black 1 U V white 2 red 3 INPUT COM1 green 4 POSITION OUTPUT 1 5V DC yellow 5 blue 6 gray 7 brown 8 FULL OPEN or FULL CLOSED SIGNAL output stem turned CCW output stem turned CW FORCED OPEN CLOSE SIGNAL output stem turned CCW output stem turned CW OVERLOAD FULL CLOSED FULL CLOSED or OVERLOAD SIGNAL Remark The yellow wire must be left unconnected if the position output sign...

Page 11: ... The following explanation applies to reverse action For di rect action read the value in the brackets Remark Applying an over torque to the adjustments may destroy stoppers or other sections of them Use a small sized screwdriver and be sure to stop turning as soon as they hit the stoppers ADJUSTMENT PROCEDURE A Zero and Span Apply power supply voltage and 0 100 input Turn ZERO adjustment until th...

Page 12: ...and Check input signal Narrow the deadband ON Flash 0 5 sec Actuator mechanism is damaged Repair Overload cause by a foreign object caught in the valve Check the valve Control PCB damaged Repair or replace Wiring error at the motor or position sensor Check the connector Low power voltage or insufficient capacity Check the power supply ON OFF Flash 2 sec Abnormal input signal Check the input signal...