Equipment configuration and commissioning test
AS-11C User Manual
7.5 Test run test steps
After the AS-11C restarts and the "HTR" indicator turns to a steady state, use FILPS to
reconnect to the AS-11C to start a trial operation test of the device.
Open the
"Operating Status"
tab in the device window, as shown in the "Figure
7.3 Operating Status Tab". At this time, you can observe the measurement
results of the AS-11C on the site and observe the output results of the monitoring
signals. The indicator light observes the output result of the output end of the I /
O interface of AS-11C, and can also test the forced control function (disarm /
force alarm) through the external switch.
Open the
"running status"
tab, in the "I/O interface" column, as shown in "Figure
7.4 I/O interface status" and "Figure 7.5 output terminal status Control, use
external switch and indicator light to test functions such as I/O reading, I/O output
setting and I/O output setting.
Related Reading
Please read the "trial run test" section of the "AS-11C
concise user manual" to learn test preparation and basic test
steps, and design other test methods as needed.