SD

ELECTRONIC FAN SPEED 
CONTROLLER

PRODUCT DESCRIPTION

These infinitely variable fan speed controllers allow you to manually adjust the 
rotational speed of single phase AC motors by varying the motor voltage through 
phase angle control. The integrated AC switch enables or disables the motor.  

ARTICLE CODES

Output regulation from low to high

Code

Current range [A] 

SDY-1-15-DT

 1—1,5

SDY-1-30-DT

0,2—3

Output regulation from high to low

Code

Current range [A] 

SDX-1-15-DT

 1—1,5

SDX-1-30-DT

0,2—3

INTENDED AREA OF USE

 

Manual control of the motor / fan speed in HVAC applications

 

For indoor use only

TECHNICAL DATA

 

Supply voltage: 230 VAC / 50—60 Hz

 

Regulated output to motor: Umin—Us

 

Unregulated output: 230 VAC / max. 2 A

 

Minimum speed adjustment by trimmer: 80—180 VAC

 

Speed control:

 

SDY—from low to high

 

SDX—from high to low

 

Enclosure: 

 

External: ASA, white colour (28049P ), IP54 (according to EN 60529)

 

Internal: polyamide, natural colour, IP44 (according to EN 60529)

 

Operating ambient conditions:

 

temperature: 0—40 °C

 

rel. humidity: 5—95 % rH (non-condensing)

STANDARDS

 

Low Voltage Directive 2014/35/EU 

 

 EN 60529:1991 Degrees of protection provided by enclosures (IP Code) 
Amendment AC:1993 to EN 60529

 

 EN 60730-1:2011 Automatic electrical controls for household and similar use - 
Part 1: General requirements

 

EMC directive 2014/30/EU:

 

 EN 60730-1:2011 Automatic electrical controls for household and similar use - 
Part 1: General requirements

 

 EN 61000-6-1:2007 Electromagnetic compatibility (EMC) - Part 6-1: Generic 
standards - Immunity for residential, commercial and light industrial environments

 

 EN 61000-6-3:2007 Electromagnetic compatibility (EMC) - Part 6-3: Generic 
standards - Emission standard for residential, commercial and light-industrial 
environments Amendments A1:2011 and AC:2012 to EN 61000-6-3

 

WEEE Directive 2012/19/EU

 

RoHs Directive 2011/65/EU

Summary of Contents for SD

Page 1: ...SD ELECTRONIC FAN SPEED CONTROLLER Mounting and operating instructions ...

Page 2: ...LLER Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 5 OPERATING INSTRUCTIONS 7 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 ...

Page 3: ...oduct performance Make sure the work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disco...

Page 4: ...control SDY from low to high SDX from high to low Enclosure External ASA white colour 28049P IP54 according to EN 60529 Internal polyamide natural colour IP44 according to EN 60529 Operating ambient conditions temperature 0 40 C rel humidity 5 95 rH non condensing STANDARDS Low Voltage Directive 2014 35 EU EN 60529 1991 Degrees of protection provided by enclosures IP Code Amendment AC 1993 to EN 6...

Page 5: ...age connected to L1 and N Uout Us Umin range 60 Min Max Off Switch On 0 30 Potentiometer position Uout Us Umin range 60 Min Max 0 30 Potentiometer position To disable the OFF position connect the 230 VAC supply voltage to the unregulated output L1 In this case do not connect the power supply to L ATTENTION WIRING AND CONNECTIONS L Power supply line 230 VAC 10 50 60 Hz N Power supply neutral L1 Unr...

Page 6: ...the wiring according to the wiring diagram see Fig 1 Wiring and connections 5 Mount the internal enclosure into the wall according to the mounting dimensions shown in Fig 2 Mounting dimensions flush mounting Fig 1 Wiring and connections Power Supply 230 VAC 50 60 HZ Unregulated output 230 VAC 10 50 60 Hz Imax 2 A Regulated output to motor Minimum speed adjustment trimmer factory pre set to 100 VAC...

Page 7: ... surface by means of the screws and dowels adhering to the mounting dimensions shown in Fig 3 Mounting dimensions surface mounting Fig 3 Mounting dimensions surface mounting 64 64 82 89 63 5 82 Correct Incorrect 5 Insert the cables through the grommets 6 Do the wiring according to the wiring diagram see Fig 1 Wiring and connections 7 Insert the internal enclosure into the external one and fix it u...

Page 8: ...if the right voltage is applied all connections are correct the machine to be regulated is functioning TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibil...