www.sentera.eu
MIW-RDCV-EN-002 - 27 / 04 / 2017
7 - 17
5.
Mount the internal enclosure into the wall by inserting suitable connecting
elements (not delivered) into the openings. Mind the correct position and
mounting dimensions shown in
Fig. 2
and
Fig. 4
.
Fig. 2 Mounting dimensions - inset mounting
82
91
10 38
52
7
6.
Put back the frame cover of the enclosure.
7.
Switch on the power supply.
8.
Customise the factory settings to the desired ones via the 3-button interface,
the 3SModbus software or via the Sensistant. For the default factory setting
see
Table
Adjustable parameters
below.
For surface mounting
1.
Disconnect the power supply.
2.
Remove the frame cover of the enclosure.
3.
Take out the internal enclosure.
4.
Mount the external enclosure to the wall using the delivered dowels and screws.
Mind the correct position and mounting dimensions shown in
Fig. 3
and
Fig. 4
.
5.
Insert the connecting cables through the grommets of the unit.
Fig. 3 Mounting dimensions - surface mounting
Fig. 4 Mounting position
64
64
2X
ø4,3
fix
fix
Acceptable
Not acceptable
6.
Do the wiring according to the wiring diagram (see
) using the information
from section “
ATTENTION
If an AC power supply is used with any of the units in a Modbus network, the
GND terminal should NOT BE CONNECTED to other units on the network or
via the CNVT‑USB‑RS485 converter. This may cause permanent damage to the
communication semiconductors and / or the computer!
7.
Put the internal enclosure into the external one and fix it using the delivered
screws and washers. (
8.
Put back the frame cover of the enclosure.
RDCV
RESIDENTIAL HVAC
CONTROLLER