Manual (slave) mode
HOLDING REGISTERS (Read / write)
Data type
Description
Data
Default Values
40001 Device slave address unsigned int.
Modbus device address
1—247
1
40002 Modbus baud rate
unsigned int.
Modbus communication baud rate
0—6
2
0 =
1 =
2 =
3 =
4 =
5 =
6 =
4.800
9.600
19.200
38.400
57.600
115.200
230.400
40003 Modbus parity mode unsigned int.
Modbus parity check mode
0—2
1
0 =
1 =
2 =
8N1
8E1
8O1
40004 Device type
unsigned int.
Device type (read-only)
2300
2300 =
RDCV9-AD
40005 HW version
unsigned int.
Hardware version of the device (read-only)
XXXX
0 x 0100 =
HW version 1.0
40006 FW version
unsigned int.
Firmware version of the device (read-only)
XXXX
0 x 0300 =
FW version 3.0
40007-
40008
Reserved, return 0
40009 Steps
unsigned int.
Starting step. Active when the number of the steps (40009) > 0
0—9
0
0 =
1 =
9 =
1 % per step
2 steps: Min / Max
10 steps
40010 Start step
unsigned int.
Starting step
0—9
0
0 =
1 =
Start at the first step
Start at the second step
40011
Minimum output
value
unsigned int.
Sets the minimum value of output signal
0—80
20
20 = 2 VDC / 4 mA / 20 % PWM
40012
Maximum output
value
unsigned int.
Sets the maximum value of output signal
20—100
100
80 = 8 VDC / 16 mA / 80 % PWM
40013 Overwrite mode
unsigned int.
Selection of overwrite mode.
0—1
0
0 =
1 =
Inactive
Active
40014 Overwrite value
unsigned int.
Output value in overwrite mode in %
0—100
50
50 =
50 %
40015 Output mode
unsigned int.
Selection of the output mode: Voltage / Current / PWM
0—2
0
0 =
1 =
2 =
0—10 VDC
0—20 mA
PWM
40016 PWM output
unsigned int.
Selection of the PWM output type: Open collector (OC) /
Pull-up +12 VDC.
0—1
0
0 =
1 =
Open collector
Pull-up +12 VDC
40017 Run / Stand-by
unsigned int.
Selection of Run / Stand-by mode
0—1
0
0 =
1 =
Run
Stand-by
40018 Start output value
unsigned int.
Start value of the output signal. Active when steps number (40009) = 0.
0—100
20
20 = 2 VDC / 4 mA / 20 % PWM
40019
Reserved, returns 0
40020
Network Bus
Termination
Resistor (NBT)
unsigned int.
Sets the unit as first or last unit on the line by connecting NBT resistor
0—1
0
0 =
1 =
Disconnected (NBT open)
Connected (NBT closed)
Note:
The holding registers can be managed via the following Modbus commands: “Read Holding Registers”, “Write Single Register” or “Write Multiple Registers”.
If you want to find out more about Modbus over serial line, please visit:
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf