Fig. 1 Wiring and connections

Output voltage

Power supply

Dry contact for 

remote ON/OFF

4. 

 Mount the internal enclosure into the wall adhering to the mounting dimensions 
shown in 

Fig. 2

.

Fig. 2 Mounting dimensions - inset mounting

82

89

26

33

50x50

62

62

60

NOTE

Mount the unit so that the terminal block and connections are at the lower side.

5. 

To select the output type, use the jumper shown in 

Fig. 3.

 

6. 

 

Adjust the minimum and maximum output speed trimmers using a screwdriver. 
See 

Fig. 4

.

Fig. 3 Output selection jumper

Fig. 4 Trimmers

7. 

Mount back the cover and secure it with the nut. 

8. 

Put back the knob and turn it to off position.

9. 

Turn on the power supply.

 Vmin adjustment 

trimmer 

 Vmax adjustment 

trimmer

MTV-1-CP

  

230 VAC POTENTIOMETER WITH MIN 
& MAX SETTINGS, DRY CONTACT

Summary of Contents for MTV-1-CP

Page 1: ...MTV 1 CP 230 VAC POTENTIOMETER WITH MIN MAX SETTINGS DRY CONTACT Mounting and operating instructions ...

Page 2: ...SCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 5 VERIFICATION OF INSTALLATION INSTRUCTIONS 7 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 MTV 1 CP 230 VAC POTENTIOMETER WITH MIN MAX SETTINGS DRY CONTACT ...

Page 3: ...d condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts always treat the product as if it is live Always disconnect the power supply before con...

Page 4: ...lications where a 0 10 VDC 0 20 mA or PWM control signal is required For indoor use only TECHNICAL DATA Power supply 230 VAC 10 50 60 Hz Load 1 10 VDC mode 2 kΩ RL 2 kΩ 2 20 mA mode 500 Ω RL 500 Ω 10 100 PWM mode 2 kΩ RL 2 kΩ Selectable output 1 10 VDC 2 20 mA 10 100 PWM Minimum output setting Vmin 1 7 VDC 2 10 mA 10 70 PWM Maximum output setting Vmax 3 10 VDC 6 20 mA 30 100 PWM Dry contact CS clo...

Page 5: ...ontact for remote ON OFF switching Out Output voltage 0 10 VDC 0 20 mA PWM Connections Cable cross section max 1 5 2 5 mm2 MOUNTING INSTRUCTIONS IN STEPS Before you start mounting your potentiometer read carefully Safety and Precautions and follow the steps For inset mounting 1 Remove the knob by turning it to the right until it pops out 2 Unscrew the nut to remove the cover of the external enclos...

Page 6: ...0 62 62 60 NOTE Mount the unit so that the terminal block and connections are at the lower side 5 To select the output type use the jumper shown in Fig 3 6 Adjust the minimum and maximum output speed trimmers using a screwdriver See Fig 4 Fig 3 Output selection jumper Fig 4 Trimmers 7 Mount back the cover and secure it with the nut 8 Put back the knob and turn it to off position 9 Turn on the powe...

Page 7: ...g the screws and washers included in the set NOTE Mount the unit so that the terminal block and connections are at the lower side 7 To select the output type use the jumper shown in Fig 3 8 Adjust the minimum and maximum output speed trimmers using a screwdriver See Fig 4 9 Mount back the cover and secure it with the nut 10 Put back the knob and turn it to off position 11 Turn on the power supply ...

Page 8: ...lieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should be disconnected from the supply Pay attention that no fluids...

Reviews: