www.sentera.eu
MIW-MTV-1-CP-EN-000 - 22 / 08 / 2018
4 - 8
back to the table of contents
PRODUCT DESCRIPTION
The potentiometer uses a supply of 230 VAC, and gives a stepless output signal
(1—10 VDC, 2—20 mA or 10—100 % PWM). The minimum output values can be
adjusted within 1—7 VDC / 2—14 mA / 10—70 % PWM, and the maximum values
- within 3—10 VDC / 6—20 mA / 30—100 % PWM. There is an additional switch
on/off function (e.g. for controller remote on/off ).
ARTICLE CODES
Article code
Supply
Output
MTV-1/010-CP
230 VAC ±10 % / 50—60 Hz
Vmin—Vmax
INTENDED AREA OF USE
■
Applications where a 0—10 VDC, 0—20 mA or PWM control signal is required
■
For indoor use only
TECHNICAL DATA
■
Power supply: 230 VAC ±10 % / 50—60 Hz
■
Load:
►
1—10 VDC mode: 2 kΩ (RL ≥ 2 kΩ)
►
2—20 mA mode: ≤ 500 Ω (RL ≤ 500 Ω)
►
10—100 % PWM mode: ≥ 2 kΩ (R
L
≥ 2 kΩ)
■
Selectable output: 1—10 VDC / 2—20 mA / 10—100 % PWM
■
Minimum output setting, Vmin: 1—7 VDC / 2—10 mA / 10—70 % PWM
■
Maximum output setting, Vmax: 3—10 VDC / 6—20 mA / 30—100 % PWM
■
Dry contact, CS:
►
closed: ON
►
open: OFF
■
Enclosure:
►
External: ASA, white-ivory (RAL 9010), IP54 (according to EN 60529)
►
Internal: polyamide, white-ivory (RAL 9010), IP44 (according to IEC 60335)
■
Operating ambient conditions:
►
temperature: 0—40 °C
►
rel. humidity: < 100 % rH (non-condensing)
■
Storage temperature: -10—55 °C
MTV-1-CP
230 VAC POTENTIOMETER WITH MIN
& MAX SETTINGS, DRY CONTACT