4. 

 Mount the internal enclosure into the wall according to the mounting dimensions 
shown in 

Fig. 2

 

Mounting dimensions - inset mounting. 

Fig. 2 Mounting dimensions - inset mounting

26

33

50x50

82

89

62
50

62

60

In case 24 VAC supply voltage is used, do not connect the input GND terminal 
with the output GND terminal.

ATTENTION

NOTE

Mount the unit so that the terminal block and connections are at the lower side.

5. 

Adjust the Vmin and Vmax trimmers.

6. 

Mount back the cover and secure it with the nut. 

7. 

Put back the knob and turn it to off position.

8. 

Turn on the power supply.

For surface mounting

1. 

  Remove the knob by turning it to the right until it pops out. 

2. 

Unscrew the nut to remove the cover of the external enclosure.

3. 

 Mount the external enclosure onto the surface by means of screws and dowels 
(not  included) adhering to the mounting dimensions shown in 

Fig. 3

 

Mounting 

dimensions - surface mounting.

Fig. 3 Mounting dimensions - surface mounting

82

89

69

82

62

62

4. 

 Insert the cables through the grommets.

5. 

Do the wiring according to the wiring diagram (see 

Fig. 1 

Wiring and connections

).

6. 

 Insert the internal enclosure into the external one and fix it using the screws and 
washers included in the set.

NOTE

Mount the unit so that the terminal block and connections are at the lower side.

7. 

Mount back the cover and secure it with the nut. 

8. 

Put back the knob and turn it to off position.

9. 

Turn on the power supply.

MTP-G010-AT

ACTIVE 
POTENTIOMETER

Summary of Contents for MTP-G010-AT

Page 1: ...Mounting and operating instructions MTP G010 AT ACTIVE POTENTIOMETER ...

Page 2: ... PRODUCT DESCRIPTION 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 5 VERIFICATION OF INSTALLATION INSTRUCTIONS 7 TRANSPORT AND STORAGE 7 WARRANTY AND RESTRICTIONS 7 MAINTENANCE 7 MTP G010 AT ACTIVE POTENTIOMETER ...

Page 3: ...environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connect...

Page 4: ...ounting ARTICLE CODES Article code Power supply Output MTP G010 AT 24 VAC or 24 VDC 0 10 VDC INTENDED AREA OF USE Applications where a 0 10 VDC control signal is required For indoor use only TECHNICAL DATA Power supply 24 VAC or 24 VDC Output Vmin Vmax Load RL 2 kΩ Vmin 0 7 VDC Vmax 3 10 VDC Enclosure External ASA white ivory RAL 9010 IP54 according to EN 60529 Internal polyamide white ivory RAL 9...

Page 5: ...ns Cable cross section max 2 5 mm MOUNTING INSTRUCTIONS IN STEPS Before you start mounting your potentiometer read carefully Safety and Precautions and follow the steps For inset mounting 1 Remove the knob by turning it to the right until it pops out 2 Unscrew the nut to remove the cover of the external enclosure 3 Do the wiring according to the wiring diagram see Fig 1 Wiring and connections Fig ...

Page 6: ...ce mounting 1 Remove the knob by turning it to the right until it pops out 2 Unscrew the nut to remove the cover of the external enclosure 3 Mount the external enclosure onto the surface by means of screws and dowels not included adhering to the mounting dimensions shown in Fig 3 Mounting dimensions surface mounting Fig 3 Mounting dimensions surface mounting 82 89 69 82 62 62 4 Insert the cables t...

Page 7: ...onditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance ...

Reviews: