OPERATIONAL DIAGRAM
MTP-G010-AT
Output, VDC
Max
10 VDC
Vmax
Vmin
Min.
0 VDC
3 VDC
7 VDC
Off
On
Potentiometer position
WIRING AND CONNECTIONS
24 VAC / DC (+)
Supply voltage, 24 VAC or +24 VDC
24 VAC / DC (-)
Supply voltage, 24 VAC or GND
Vout (-)
Output signal, GND
Vout (+)
Output voltage, 0—10 VDC
Connections
Cable cross section: max. 2,5 mm
²
MOUNTING INSTRUCTIONS IN STEPS
Before you start mounting your potentiometer, read carefully
“Safety and Precautions”
and follow the steps:
For inset mounting
1.
Remove the knob by turning it to the right until it pops out.
2.
Unscrew the nut to remove the cover of the external enclosure.
3.
Do the wiring according to the wiring diagram (see
Fig. 1
Wiring and connections
).
Fig. 1 Wiring and connections
Vmax adjustment
trimmer
Vmin adjustment
trimmer
Supply voltage:
24 VAC or VDC
Output voltage:
0, Vmin—Vmax
GND
MTP-G010-AT
ACTIVE
POTENTIOMETER