PRODUCT DESCRIPTION

MTP-G010-AT potentiometer is intended for direct control of EC fans / motors and 
actuators. It requires a supply voltage of 24 VDC or 24 VAC and provides a stepless 
output signal that can be set by a rotary knob with off-position. The output range is 
adjustable via two internal trimmers between Vmin (0—7 VDC) and Vmax (3—10 VDC). 
Its splash-proof enclosure is suitable for both inset and surface mounting.

ARTICLE CODES

Article code

Power supply

Output

MTP-G010-AT

24 VAC or 24 VDC

0—10 VDC

INTENDED AREA OF USE

 

Applications where a 0—10 VDC control signal is required

 

For indoor use only

TECHNICAL DATA

 

Power supply: 24 VAC or 24 VDC

 

Output: Vmin—Vmax

 

Load: R

L

 ≥ 2 kΩ

 

Vmin: 0—7 VDC

 

Vmax: 3—10 VDC

 

Enclosure:

 

External: ASA, white-ivory (RAL 9010), IP54 (according to EN 60529)

 

Internal: polyamide, white-ivory (RAL 9010), IP44 (according to IEC 60335)

 

Operating ambient conditions:

 

temperature: 0—40 °C

 

rel. humidity: < 100 % rH (non-condensing)

 

Storage temperature: -10—55 °C

STANDARDS

 

Low Voltage Directive 2014/35/EC 

 

EMC Directive 2014/30/EC

 

WEEE Directive 2012/19/EC

 

RoHs Directive 2011/65/EC

MTP-G010-AT

ACTIVE 
POTENTIOMETER

Summary of Contents for MTP-G010-AT

Page 1: ...Mounting and operating instructions MTP G010 AT ACTIVE POTENTIOMETER ...

Page 2: ... PRODUCT DESCRIPTION 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 5 VERIFICATION OF INSTALLATION INSTRUCTIONS 7 TRANSPORT AND STORAGE 7 WARRANTY AND RESTRICTIONS 7 MAINTENANCE 7 MTP G010 AT ACTIVE POTENTIOMETER ...

Page 3: ...environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connect...

Page 4: ...ounting ARTICLE CODES Article code Power supply Output MTP G010 AT 24 VAC or 24 VDC 0 10 VDC INTENDED AREA OF USE Applications where a 0 10 VDC control signal is required For indoor use only TECHNICAL DATA Power supply 24 VAC or 24 VDC Output Vmin Vmax Load RL 2 kΩ Vmin 0 7 VDC Vmax 3 10 VDC Enclosure External ASA white ivory RAL 9010 IP54 according to EN 60529 Internal polyamide white ivory RAL 9...

Page 5: ...ns Cable cross section max 2 5 mm MOUNTING INSTRUCTIONS IN STEPS Before you start mounting your potentiometer read carefully Safety and Precautions and follow the steps For inset mounting 1 Remove the knob by turning it to the right until it pops out 2 Unscrew the nut to remove the cover of the external enclosure 3 Do the wiring according to the wiring diagram see Fig 1 Wiring and connections Fig ...

Page 6: ...ce mounting 1 Remove the knob by turning it to the right until it pops out 2 Unscrew the nut to remove the cover of the external enclosure 3 Mount the external enclosure onto the surface by means of screws and dowels not included adhering to the mounting dimensions shown in Fig 3 Mounting dimensions surface mounting Fig 3 Mounting dimensions surface mounting 82 89 69 82 62 62 4 Insert the cables t...

Page 7: ...onditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance ...

Reviews: