MIW-FCMFX-R-EN-000 - 08 / 07 / 2020

9 - 9

back to the table of contents

3. 

 When the red LED is on, the measured value (temperature, relative humidity or 
CO

2

) is below the minimum measurement range value or above the maximum 

value. Blinking red LED indicates loss of communication with a sensor (

Fig. 6 - 3

). 

Fig. 6 LED indications

3

2

1

NOTE

By default, the LED indication refers to temperature measurements. This can be 
changed to relative humidity or CO

2

 values via Modbus Holding Register 79 (see 

Table

 Holding registers 

below

).

Ambient light sensor

The measured light intensity in lux is available in Input Register 41. Additionally, 
an active and standby level can be defined in Holding registers 35 and 36. Input 
Register 42  indicates if the measured value is below standby level, above active 
level or in between both levels:

 

 Ambient light level < standby level: Input Register 42 indicates “Standby”.

 

 Ambient light level > active level:  Input Register 42 indicates “Active”. 

 

 Standby level < Ambient light level < Active level: Input Register 42 indicates “Low 
intensity”. 

VERIFICATION OF INSTALLATION

After switching on the power supply one of the LEDs lights up according to the 
status of the measured variable. If this is not the case, check the connections.

TRANSPORT AND STORAGE

Avoid shocks and extreme conditions; stock in original packing.

WARRANTY AND RESTRICTIONS

Two years from the delivery date against defects in manufacturing. Any modifications 
or alterations to the product after the date of publication relieve the manufacturer 
of any responsibilities. The manufacturer bears no responsibility for any misprints or 
mistakes in this data. 

MAINTENANCE

In normal conditions this product is maintenance-free. If soiled, clean with a dry or 
damp cloth. In case of heavy pollution, clean with a non-aggressive product. In these 
circumstances the unit should be disconnected from the supply. Pay attention that 
no fluids enter the unit. Only reconnect it to the supply when it is completely dry.

FCMFX-R

INTELLIGENT MULTIFUNCTIONAL 
SENSOR

Summary of Contents for FCMFF-R

Page 1: ...Mounting and operating instructions FCMFX R INTELLIGENT MULTIFUNCTIONAL SENSOR ...

Page 2: ... ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 6 MOUNTING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 8 VERIFICATION OF INSTALLATION 9 TRANSPORT AND STORAGE 9 WARRANTY AND RESTRICTIONS 9 MAINTENANCE 9 FCMFX R INTELLIGENT MULTIFUNCTIONAL SENSOR ...

Page 3: ...rk environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before conn...

Page 4: ...d commercial buildings Demand controlled ventilation For indoor use only TECHNICAL DATA Demand controlled ventilation based on T rH and CO2 Analogue modulating output type 0 10 VDC mode RL 50 kΩ 0 20 mA mode RL 500 Ω PWM open collector type mode PWM Frequency 1 kHz min RL 50 kΩ PWM voltage level 3 3 or 12 VDC Selectable temperature range 0 50 C Selectable relative humidity range 0 100 Selectable C...

Page 5: ...residential commercial and light industrial environments Amendments A1 2011 and AC 2012 to EN 61000 6 3 EN 61326 1 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 1 General requirements EN 61326 2 3 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 2 3 Particular requirements Test configuration operational conditio...

Page 6: ...ground of the analogue output is internally connected with the ground of the power supply For this reason G and F types cannot be used together on the same network Never connect the common ground of G type articles to other devices powered by a DC voltage Doing so might cause permanent damage to the connected devices ATTENTION MOUNTING INSTRUCTIONS IN STEPS Before you start mounting the unit read ...

Page 7: ...r surface mounting 1 Disconnect the power supply 2 Remove the frame cover of the enclosure 3 Take out the internal enclosure 4 Mount the external enclosure onto the wall using the dowels and screws included in the set Mind the correct position and mounting dimensions shown in Fig 4 and Fig 5 5 Insert the connecting cables through the grommets of the unit Fig 4 Mounting dimensions surface mounting ...

Page 8: ...that the terminal block and connections are at the lower side ATTENTION Do not expose to direct sunlight OPERATING INSTRUCTIONS The unit is supplied with electrical energy at voltages high enough to inflict personal injury or threat to health ATTENTION Calibration procedure Sensor calibration is not necessary All sensor elements are calibrated and tested in our factory In the unlikely event of CO2...

Page 9: ... level active level Input Register 42 indicates Active Standby level Ambient light level Active level Input Register 42 indicates Low intensity VERIFICATION OF INSTALLATION After switching on the power supply one of the LEDs lights up according to the status of the measured variable If this is not the case check the connections TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in ori...

Reviews: