WIRING AND CONNECTIONS 

Article type

FCMFF-R

FCMFG-R

V+

18—34 VDC

18—34 VDC

15—24 VAC ±10%

V-

Ground

Common ground

*

AC ~

*

A

Modbus RTU (RS485), signal A

/B

Modbus RTU (RS485), signal /B

Ao

Analogue / modulating output - T, rH or CO

2

 

(0—10 VDC / 0—20 mA / PWM)

GND

Ground AO

Common ground

*

Connections

Spring contact terminal block, cable cross section: 2,5 mm

2

; pitch 

5 mm; shielded cable

The -F version of the product is not suited for 3-wire connection. It has separate 
grounds for power supply and analogue output. Connecting both grounds together 
might result in incorrect measurements. Minimum 4 wires are required to connect 
-F type sensors.
The -G version is intended for 3-wire connection and features a ‘common ground’. 
This means that the ground of the analogue output is internally connected with 
the ground of the power supply. For this reason, -G and -F types cannot be used 
together on the same network. Never connect the common ground of -G type 
articles to other devices powered by a DC voltage. Doing so might cause permanent 
damage to the connected devices.

ATTENTION

MOUNTING INSTRUCTIONS IN STEPS

Before you start mounting the unit, read carefully 

“Safety and Precautions”

Then proceed with the following steps:

ATTENTION

When planning the installation, allow enough clearance for maintenance and 
service. Mount the sensor in a well-ventilated area.

1. 

Disconnect the supply voltage.

2. 

Remove the cover of the enclosure and take the controller out of the housing, so 
that it can be easily connected. 

3. 

 Do the wiring according to the wiring diagram (see 

Fig. 1

).

Fig. 1 Wiring and connections

Supply voltage:

FCMFF-R: 18—34 VDC 
FCMFG-R: 18—34 VDC / 15—24 VAC ±10 %

Modbus 

RTU

/B

A

Analogue / modulating 

output

FCMFX-R

INTELLIGENT MULTIFUNCTIONAL 
SENSOR

Summary of Contents for FCMFF-R

Page 1: ...Mounting and operating instructions FCMFX R INTELLIGENT MULTIFUNCTIONAL SENSOR ...

Page 2: ... ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 6 MOUNTING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 8 VERIFICATION OF INSTALLATION 9 TRANSPORT AND STORAGE 9 WARRANTY AND RESTRICTIONS 9 MAINTENANCE 9 FCMFX R INTELLIGENT MULTIFUNCTIONAL SENSOR ...

Page 3: ...rk environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before conn...

Page 4: ...d commercial buildings Demand controlled ventilation For indoor use only TECHNICAL DATA Demand controlled ventilation based on T rH and CO2 Analogue modulating output type 0 10 VDC mode RL 50 kΩ 0 20 mA mode RL 500 Ω PWM open collector type mode PWM Frequency 1 kHz min RL 50 kΩ PWM voltage level 3 3 or 12 VDC Selectable temperature range 0 50 C Selectable relative humidity range 0 100 Selectable C...

Page 5: ...residential commercial and light industrial environments Amendments A1 2011 and AC 2012 to EN 61000 6 3 EN 61326 1 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 1 General requirements EN 61326 2 3 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 2 3 Particular requirements Test configuration operational conditio...

Page 6: ...ground of the analogue output is internally connected with the ground of the power supply For this reason G and F types cannot be used together on the same network Never connect the common ground of G type articles to other devices powered by a DC voltage Doing so might cause permanent damage to the connected devices ATTENTION MOUNTING INSTRUCTIONS IN STEPS Before you start mounting the unit read ...

Page 7: ...r surface mounting 1 Disconnect the power supply 2 Remove the frame cover of the enclosure 3 Take out the internal enclosure 4 Mount the external enclosure onto the wall using the dowels and screws included in the set Mind the correct position and mounting dimensions shown in Fig 4 and Fig 5 5 Insert the connecting cables through the grommets of the unit Fig 4 Mounting dimensions surface mounting ...

Page 8: ...that the terminal block and connections are at the lower side ATTENTION Do not expose to direct sunlight OPERATING INSTRUCTIONS The unit is supplied with electrical energy at voltages high enough to inflict personal injury or threat to health ATTENTION Calibration procedure Sensor calibration is not necessary All sensor elements are calibrated and tested in our factory In the unlikely event of CO2...

Page 9: ... level active level Input Register 42 indicates Active Standby level Ambient light level Active level Input Register 42 indicates Low intensity VERIFICATION OF INSTALLATION After switching on the power supply one of the LEDs lights up according to the status of the measured variable If this is not the case check the connections TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in ori...

Reviews: