MIW-FCMFX-R-EN-000 - 08 / 07 / 2020

8 - 9

back to the table of contents

10. 

   Customise the factory settings to the desired ones via the 3SModbus software 
or the Sensistant configurator. For the default factory settings, see the  

Modbus 

register map

.

Optional settings

To assure correct communication, the NBT needs to be activated in only two devices 
on the Modbus RTU network. If necessary, enable the NBT resistor via 3SModbus or 
Sensistant (

Holding register 9

).

 

Example 1

Example 2

RX

ТX

NBT

NBT

Slave 2

Master

Slave n

Slave 1

Slave 2

Slave 1

RX

ТX

NBT

NBT

Master

Slave n

NOTE

On a Modbus RTU network, two bus terminators (NBTs) need to be activated.

For the complete Modbus register data, refer to the product Modbus Register 
Map, which is a separate document attached to the article code on the website 
and contains the registers list. Products with earlier firmware versions may not be 
compatible with this list. 

NOTE

NOTE

Mount the unit so that the terminal block and connections are at the lower side.

ATTENTION

Do not expose to direct sunlight!

OPERATING INSTRUCTIONS

The unit is supplied with electrical energy at voltages high enough to inflict personal 
injury or threat to health. 

ATTENTION

Calibration procedure:

Sensor calibration is not necessary. All sensor elements are calibrated and tested in 
our factory.
In the unlikely event of CO

2

 sensor element failure, this component can be replaced. 

Bootloader

Thanks to the bootloader functionality, the unit firmware can be updated via Modbus 
RTU communication. With 3SM boot Application (part of 3SM center software 
suite), ‘boot mode’ is automatically activated and the firmware can be updated.

NOTE

Make sure the power supply does not get interrupted during “bootload” procedure, 
otherwise you risk losing unsaved data. 

LED indications

1. 

 When the green LED is on, the measured value (temperature, relative humidity or 
CO

2

) is between the minimum and maximum alert range values (

Fig. 6 - 1

).

2. 

 When the yellow LED is on, the measured value (temperature, relative humidity 
or CO

2

) is in the alert range (

Fig. 6 - 2

).

FCMFX-R

INTELLIGENT MULTIFUNCTIONAL 
SENSOR

Summary of Contents for FCMFF-R

Page 1: ...Mounting and operating instructions FCMFX R INTELLIGENT MULTIFUNCTIONAL SENSOR ...

Page 2: ... ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 6 MOUNTING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 8 VERIFICATION OF INSTALLATION 9 TRANSPORT AND STORAGE 9 WARRANTY AND RESTRICTIONS 9 MAINTENANCE 9 FCMFX R INTELLIGENT MULTIFUNCTIONAL SENSOR ...

Page 3: ...rk environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before conn...

Page 4: ...d commercial buildings Demand controlled ventilation For indoor use only TECHNICAL DATA Demand controlled ventilation based on T rH and CO2 Analogue modulating output type 0 10 VDC mode RL 50 kΩ 0 20 mA mode RL 500 Ω PWM open collector type mode PWM Frequency 1 kHz min RL 50 kΩ PWM voltage level 3 3 or 12 VDC Selectable temperature range 0 50 C Selectable relative humidity range 0 100 Selectable C...

Page 5: ...residential commercial and light industrial environments Amendments A1 2011 and AC 2012 to EN 61000 6 3 EN 61326 1 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 1 General requirements EN 61326 2 3 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 2 3 Particular requirements Test configuration operational conditio...

Page 6: ...ground of the analogue output is internally connected with the ground of the power supply For this reason G and F types cannot be used together on the same network Never connect the common ground of G type articles to other devices powered by a DC voltage Doing so might cause permanent damage to the connected devices ATTENTION MOUNTING INSTRUCTIONS IN STEPS Before you start mounting the unit read ...

Page 7: ...r surface mounting 1 Disconnect the power supply 2 Remove the frame cover of the enclosure 3 Take out the internal enclosure 4 Mount the external enclosure onto the wall using the dowels and screws included in the set Mind the correct position and mounting dimensions shown in Fig 4 and Fig 5 5 Insert the connecting cables through the grommets of the unit Fig 4 Mounting dimensions surface mounting ...

Page 8: ...that the terminal block and connections are at the lower side ATTENTION Do not expose to direct sunlight OPERATING INSTRUCTIONS The unit is supplied with electrical energy at voltages high enough to inflict personal injury or threat to health ATTENTION Calibration procedure Sensor calibration is not necessary All sensor elements are calibrated and tested in our factory In the unlikely event of CO2...

Page 9: ... level active level Input Register 42 indicates Active Standby level Ambient light level Active level Input Register 42 indicates Low intensity VERIFICATION OF INSTALLATION After switching on the power supply one of the LEDs lights up according to the status of the measured variable If this is not the case check the connections TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in ori...

Reviews: