www.sentera.eu
MIW-EVSS-DM-EN-000 - 18 / 12 / 2018
12 - 16
MODBUS REGISTER MAPS
MODBUS REGISTER MAPS
INPUT REGISTERS
Data type
Description
Data
Values
1
Analog input level
unsigned int.
Analog input value depending on the selected analog
input type.
0—100
0 =
100 =
0 =
100 =
0 VDC
10,0 VDC
or
0 mA
20,0 mA
2
Current output voltage
unsigned int.
Actual output voltage
0
30—100
0 =
30 =
100 =
0 % Us
30 % Us
100 % Us
3
Analog input type
unsigned int.
Type of the selected analog input
0—1
0 =
1 =
0—20 mA
0—10 VDC
4
Ascending / descending
input mode
unsigned int.
Ascending or descending analog input mode depending
on the selected analog input type.
0—1
0 =
1 =
0 =
1 =
10—0 VDC
0—10 VDC
or
20—0 mA
0—20 mA
5
Maximum output
voltage
unsigned int.
Maximum output voltage
75—100
75 =
100 =
75 % Us
100 % Us
6
Minimum output
voltage
unsigned int.
Minimum output voltage
30—70
30 =
70 =
30 % Us
70 % Us
7
Enable off level
unsigned int.
Enables off level
0—1
0 =
1 =
Disabled
Enabled
8
Off level value
unsigned int.
Off level value depending on the selected analog
input type and ascending / descending analog input
mode.
0—40
60—100
Ascending mode:
0 =
400 =
0 =
200 =
Voltage
0 VDC
4,0 VDC
Current
0 mA
8,0 mA
Descending mode:
100 =
60 =
100 =
60 =
Voltage
10,0 VDC
6,0 VDC
Current
20,0 mA
12,0 mA
9
Kick start / soft start
unsigned int.
Selects kick start or soft start
0—1
0 =
1 =
soft start
kick start
10
Remote control input
unsigned int.
Remote control input
0—1
0 =
1 =
Disabled
Enabled
12
L1 control
unsigned int.
L1 control
0—1
0 =
1 =
Off
On
13
Alarm LED
unsigned int.
Alarm LED
0—1
0 =
1 =
Off
On
14
ON/Stand-by LED
unsigned int.
ON/Stand-by LED
0—2
0 =
1 =
2 =
Off
On
Stand-by
15-20
Reserved, return 0
EVSS
ELECTRONIC FAN SPEED