background image

www.sentera.eu

MIW-EVSS-DM-EN-000 - 18 / 12 / 2018

15 - 16

back to the table of contents

the analog input signal is below the value of the OFF level (if enabled) or when the 
remote control input is disabled, the output voltage of the unregulated output L1 is 
0 = OFF (0 VAC). Otherwise it is 1 = On (230 VAC).

Input Register 13

 (30013) shows the status of the alarm LED (

Fig. 10

). It indicates 

motor overheating. When the register value is ‘0’ = Off, there is no overheating and 
when the value is ‘1’ = On, the overheating is detected and the controller stops the 
motor.

Input Register 14

 (30014) shows the operating status of the unit. When the register 

value is 0 (Off), the controller is switched off. The ON/Stand-by LED on the front 
panel is off. See 

Fig. 10

 

Operating indication

When the value is ‘1’ (On), the controller operates according to the control algorithm, 
and the analog input signal is above the selected OFF level value (if enabled). The 
ON/Stand-by LED (

Fig. 10

) gives out continuous light. 

The ON/Stand-by LED blinks and the register value is 2 (Stand-by) when OFF level is 
enabled and the analog input signal is below the OFF level value.

HOLDING REGISTERS

 (See Table 1 

Modbus register maps

)

These registers are read  /  write registers and they can be managed with “Read 
Holding Registers” command, “Write single register” and “Write Multiple Registers” 
commands. They are organised in parts containing different kind of information. The 
holding registers that are not used are read only. Writing values on these registers 
does not return Modbus error exception; however, it does not change anything 
either!

 

Part 1: 

This part contains information about the unit and Modbus communication settings. 

Holding register 1

 (40001) contains the address at which the controller replies to 

the Modbus master unit. The default address is ‘1’. You can change it in two ways: 
1.  Send command “Write Single Register” with address ‘1’ and write the new 

address value.

2.  Connect only your unit to a master controller or PC application and send the 

command “Write Single Register” to address ‘0’ (Modbus broadcast address) 
and write a new address value.

The next two registers (2 and 3)

 contain Modbus settings. Changing these registers 

you change the communication settings. The default Modbus settings are 19200-E-1 
as it is stated in the Modbus Protocol Specification.

The next three registers (4, 5 and 6)

 are read only. They contain information about 

the hardware and firmware versions.

Holding register 7 

(40007) sets the operation mode of the controller. There are two 

options: Standalone mode and Modbus mode. In Standalone mode the controller is 
fully controlled by the analog input signal and the selected hardware settings. In 
Modbus mode the settings can be controlled by the Modbus master controller.

Holding register 8 

(40008) is used for output override control. This setting is used 

to override output voltage by a preselected value. This value has greater priority 
over the calculated output voltage of the integrated control algorithm. Only kick 
start / soft start can change the output voltage value.

Holding registers 9

 (40009) and 10 (40010) are not used. They are read only. 

 

Part 2: 

Holding register 11

 (40011) sets the analog input signal type. The default value is ‘1’ 

(0—10 VDC). ‘0’ is for 0—20 mA. 

Holding register 12

 (40012) defines the ascending / descending analog input mode. 

The default value is ‘1’ is for 0—10 VDC (ascending voltage signal). The register values 
are ‘0’ for 10—0 VDC and ‘1’ for 0—10 VDC when voltage signal is selected, and ‘0’ 
for 20— 0  mA and ‘1’ for 0—20 mA when current signal is selected.

Holding register 13

 (40013) sets the maximum output voltage. The default value 

is ‘100’ (100 % Us or 230 VAC). The register values vary in the range of 75—100 
(75—100 % Us). 

Holding register 14

 (40014) sets the minimum output voltage. The default value is 

‘30’ (30 % Us). The register values vary in the range of 30—70 (30—70 % Us). 

EVSS

ELECTRONIC FAN SPEED 
CONTROLLER WITH TK

Summary of Contents for EVSS Series

Page 1: ...EVSS ELECTRONIC FAN SPEED CONTROLLER WITH TK Mounting and operating instructions ...

Page 2: ...NDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING AND CONNECTIONS 5 OPERATIONAL DIAGRAMS 6 MOUNTING INSTRUCTIONS IN STEPS 8 VERIFICATION OF INSTALLATION INSTRUCTIONS 10 OPERATING INSTRUCTIONS 11 MODBUS REGISTER MAPS 12 TRANSPORT AND STORAGE 16 WARRANTY AND RESTRICTIONS 16 MAINTENANCE 16 EVSS ELECTRONIC FAN SPEED CONTROLLER WITH TK ...

Page 3: ...ment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting ser...

Page 4: ...speed control in ventilation systems For indoor use only TECHNICAL DATA Power supply 230 VAC 10 50 60 Hz Analog input voltage 0 10 VDC 10 0 VDC current 0 20 mA 20 0 mA Analog input modes ascending or descending Analog input functionality Normal mode Logic mode Remote control input normal or timer functionality Regulated output 30 100 Us Max output load depends on the version Unregulated output L1 ...

Page 5: ...C EN 61326 WEEE Directive 2012 19 EU RoHs Directive 2011 65 EU WIRING AND CONNECTIONS L Supply voltage 230 VAC 10 50 60 Hz N Neutral PE Earth terminal L1 Unregulated output 230 VAC max 2 A U1 U2 Regulated output to the motor TK TK Thermal contact N Neutral AL Alarm output 230 VAC 1 A SW Remote control switch A Modbus RTU RS485 signal A B Modbus RTU RS485 signal B V Supply output 12 VDC 1 mA Ai Ana...

Page 6: ...C mA 10 VDC 20 mA 6 VDC 12 mA U out 100 75 70 30 Umax range Umin range Off level Off level enabled Ascending mode calculation formula Uout Umax Aimax Off level Ai Off level Umax Umin Descending mode calculation formula Uout Umax Aimax Off level Ai Off level Umax Umin t s Umax Umin 0 Ai 10 VDC 20 mA Uout 100 75 70 30 0 VDC 0 mA Umax range Umin range Kick start time t s Umax Umin 0 Ai 10 VDC 20 mA U...

Page 7: ... off level Timer mode Logic mode 0 t s 5 VDC 2 5 VDC Remote Switch VDC Stand by Operate Voltage amplitude range Switch control signal t s 0 Uout 100 75 Umax range Kick start time Operation timer Controller is off Kick start enabled Soft start enabled t t t t SW ON ON Holding register 18 Holding register 21 Soft start duration Soft start duration Start Output Umax Timer Soft start Stop Start Stop O...

Page 8: ...ng position and Fig 2 Mounting dimensions Fig 1 Mounting dimensions Fig 2 Mounting position 140 102 4 x 4 5 0 124 205 92 Correct Incorrect 3 Connect the motor fan 4 The unregulated output L1 N can be used to connect a light indicator or to control a damper actuator a valve etc if necessary See Fig 3 Fig 3 Wiring and connections VR3 Off level adj Min speed adj Max speed adj ON 0 10v 10 0v 0 10v 0 2...

Page 9: ...manually onto the pins to be connected see Fig 5 To assure correct communication the NBT jumper needs to be activated in only two devices on the Modbus RTU network see Example 1 and Example 2 Example 1 Example 2 Fig 5 Network bus resistor jumper RX ТX NBT NBT NBT Slave 2 Master Slave n Slave 1 Slave 2 Slave 1 RX ТX NBT NBT Master Slave n ATTENTION On a Modbus RTU network two bus terminators NBTs n...

Page 10: ...ck start disabled Input voltage mode 0 10 VDC Min setting of the Min speed trimmer Max setting of the Max speed trimmer Min setting of the Off level trimmer 3 Set the analog input signal to the maximum value of 10 VDC or 20 mA 4 The connected motor will run at maximum speed or minimum speed depending on the analog input mode ascending descending 5 If OFF level is enabled and descending analog inpu...

Page 11: ... switched on When Timer mode is selected the controller receives a pulse control signal from the remote control switch When Logic mode is selected the controller receives a pulse control signal from the Ai input In both modes Timer mode and Logic mode the pulse width is to be more than 30 ms otherwise the signal is filtered FRONT PANEL LED INDICATION When the green LED on the front cover Fig 10 gi...

Page 12: ...ximum output voltage 75 100 75 100 75 Us 100 Us 6 Minimum output voltage unsigned int Minimum output voltage 30 70 30 70 30 Us 70 Us 7 Enable off level unsigned int Enables off level 0 1 0 1 Disabled Enabled 8 Off level value unsigned int Off level value depending on the selected analog input type and ascending descending analog input mode 0 40 60 100 Ascending mode 0 400 0 200 Voltage 0 VDC 4 0 V...

Page 13: ...s settable Active only if holding register 7 is set to 1 0 1 0 0 1 Disabled Enabled 16 Off level value unsigned int Off level value Depends on the selected analog input type and ascending descending analog input mode Always settable Active only if holding register 7 is set to 1 0 40 60 100 0 Ascending mode 0 40 0 40 Voltage 0 VDC 4 0 VDC Current 0 mA 8 0 mA Descending mode 100 60 100 60 Voltage 10...

Page 14: ... 4 according to the selected operating mode The values are 0 for descending mode or 1 for ascending mode Input register 5 30005 shows the value of the maximum output voltage This input register is defined by holding register 13 or the hardware setting of the Max trimmer Fig 6 according to the selected operating mode The register values vary in range of 75 100 75 100 Us VAC Input register 6 30006 s...

Page 15: ... Single Register with address 1 and write the new address value 2 Connect only your unit to a master controller or PC application and send the command Write Single Register to address 0 Modbus broadcast address and write a new address value The next two registers 2 and 3 contain Modbus settings Changing these registers you change the communication settings The default Modbus settings are 19200 E 1...

Page 16: ...ly in timer mode and or logic mode The default value is 60 60 seconds The register values can vary from 0 to 200 0 200 seconds This setting is accessible only in Modbus mode The working time is equal to the sum of the kick start soft start duration and the time value of the operation timer When a working time expires only a remote control input or analog input can restart the unit The next holding...

Reviews: