background image

www.sentera.eu

MIW-EVSS-DM-EN-000 - 18 / 12 / 2018

14 - 16

back to the table of contents

INPUT REGISTERS

 (See Table 1 

Modbus register maps

)

The input registers are read-only. Table 1 shows how the data is organized in the 
input register sector. The measured data starts from address 1 (30001) and ends at 
address 14 (30014). The other input registers are not used. When they are addressed, 
they return 0. 
All the data can be read by “Read Inputs Registers” command. Table 1 shows what 
the type of the returned data for each register is and the way it should be interpreted. 
For example reading ‘300’ in input register 1 means that the measured analog input 
signal is 3,0 VDC (or 6,0 mA), reading ‘50’ in input register 2 means that the output 
voltage is 50 % Us (115 VAC).

Input register 1

 (30001) shows the current value of measured analog input signal. 

This value depends on the selected analog input type. When voltage input is 
selected, the values vary in the range of 0—1.000 (0—10,0 VDC). When current input 
is selected, the values vary in the range of 0—1.000 (0—20,0 mA).

Input register 2 

(30002) shows the current value of the output voltage. This input 

register is overridden by holding register 31 if output override control (holding 
register 8) is enabled. When output override control is disabled, this input register 
shows the value of the output voltage according to the selected operating mode. 
The output voltage values vary in the range of 30—100 % Us (69—230 VAC). Reading 
‘0’ (0 VAC) indicates that the controller is off. 

Input register 3

 (30003) shows the type of the analog input 

signal. This input register is defined by holding register 11 or by the 
hardware setting of position 4 of the DIP switch. The values are ‘0’ 

 

(for 0—20 mA) or ‘1’ (for 0—10 VDC).

Input register 4

 (30004) shows the selected mode of the analog input. This input 

register is defined by holding register 12 or the hardware setting of position 1 of the 
DIP switch (

Fig. 4

), according to the selected operating mode. The values are ‘0’ (for 

descending mode) or ‘1’ (for ascending mode).

Input register 5 

(30005) shows the value of the maximum output voltage. This 

input register is defined by holding register 13 or the hardware setting of the Max. 
trimmer (

Fig. 6

), according to the selected operating mode. The register values vary 

in range of 75—100 (75—100  %  Us  VAC).

Input register 6

 (30006) shows the value of the minimum output voltage. This input 

register is defined by holding register 14 or the hardware setting of Min. trimmer 
(

Fig. 7

), according to the selected operating mode. The register values vary in range 

30—70 % Us.

Input Register 7

 (30007) gives information about the OFF level state. In Standalone 

mode it contains the value set by position 2 of the DIP switch (

Fig. 4

). In Modbus 

mode it contains the value of holding register 15. It could be ‘0’ (disabled) or ‘1’ 
(enabled).

Input Register 8

 (30008) gives information about the OFF level value. In 

Standalone mode it contains the value set by the OFF level trimmer (

Fig. 8

). 

In Modbus mode it contains the value set by holding register 16. The register 
values can vary from 0 to 40 (0—4,0 VDC / 0—8,0 mA) and from 60 to 100  
(6,0—10,0 VDC / 12,0—20,0 mA). The values depend on the selected analog input 
type and mode. 

Input Register 9

 (30009) gives information about the kick start or soft start 

selection. In Standalone mode the value corresponds to the start type set by position 
3 of the DIP switch. In Modbus mode it contains the value set by holding register 17. 
The register values are ‘0’ (for soft start) or ‘1’ (for kick start).

Input Register 10 

(30010) shows the state of the remote control input. When it is 

disabled, the unit works in normal operating mode. When the remote control input is 
enabled, the controller is in stand-by mode. The register values are ‘0’ (for disabled) 
or ‘1’ (for enabled).

Input Register 11

 (30011) shows the status of the alarm relay output. It is off when 

the register value is ‘0’, and energised when the register value is ‘1’.

Input Register 12

 (30012) shows the status of the unregulated output L1. When 

EVSS

ELECTRONIC FAN SPEED 
CONTROLLER WITH TK

Summary of Contents for EVSS Series

Page 1: ...EVSS ELECTRONIC FAN SPEED CONTROLLER WITH TK Mounting and operating instructions ...

Page 2: ...NDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING AND CONNECTIONS 5 OPERATIONAL DIAGRAMS 6 MOUNTING INSTRUCTIONS IN STEPS 8 VERIFICATION OF INSTALLATION INSTRUCTIONS 10 OPERATING INSTRUCTIONS 11 MODBUS REGISTER MAPS 12 TRANSPORT AND STORAGE 16 WARRANTY AND RESTRICTIONS 16 MAINTENANCE 16 EVSS ELECTRONIC FAN SPEED CONTROLLER WITH TK ...

Page 3: ...ment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting ser...

Page 4: ...speed control in ventilation systems For indoor use only TECHNICAL DATA Power supply 230 VAC 10 50 60 Hz Analog input voltage 0 10 VDC 10 0 VDC current 0 20 mA 20 0 mA Analog input modes ascending or descending Analog input functionality Normal mode Logic mode Remote control input normal or timer functionality Regulated output 30 100 Us Max output load depends on the version Unregulated output L1 ...

Page 5: ...C EN 61326 WEEE Directive 2012 19 EU RoHs Directive 2011 65 EU WIRING AND CONNECTIONS L Supply voltage 230 VAC 10 50 60 Hz N Neutral PE Earth terminal L1 Unregulated output 230 VAC max 2 A U1 U2 Regulated output to the motor TK TK Thermal contact N Neutral AL Alarm output 230 VAC 1 A SW Remote control switch A Modbus RTU RS485 signal A B Modbus RTU RS485 signal B V Supply output 12 VDC 1 mA Ai Ana...

Page 6: ...C mA 10 VDC 20 mA 6 VDC 12 mA U out 100 75 70 30 Umax range Umin range Off level Off level enabled Ascending mode calculation formula Uout Umax Aimax Off level Ai Off level Umax Umin Descending mode calculation formula Uout Umax Aimax Off level Ai Off level Umax Umin t s Umax Umin 0 Ai 10 VDC 20 mA Uout 100 75 70 30 0 VDC 0 mA Umax range Umin range Kick start time t s Umax Umin 0 Ai 10 VDC 20 mA U...

Page 7: ... off level Timer mode Logic mode 0 t s 5 VDC 2 5 VDC Remote Switch VDC Stand by Operate Voltage amplitude range Switch control signal t s 0 Uout 100 75 Umax range Kick start time Operation timer Controller is off Kick start enabled Soft start enabled t t t t SW ON ON Holding register 18 Holding register 21 Soft start duration Soft start duration Start Output Umax Timer Soft start Stop Start Stop O...

Page 8: ...ng position and Fig 2 Mounting dimensions Fig 1 Mounting dimensions Fig 2 Mounting position 140 102 4 x 4 5 0 124 205 92 Correct Incorrect 3 Connect the motor fan 4 The unregulated output L1 N can be used to connect a light indicator or to control a damper actuator a valve etc if necessary See Fig 3 Fig 3 Wiring and connections VR3 Off level adj Min speed adj Max speed adj ON 0 10v 10 0v 0 10v 0 2...

Page 9: ...manually onto the pins to be connected see Fig 5 To assure correct communication the NBT jumper needs to be activated in only two devices on the Modbus RTU network see Example 1 and Example 2 Example 1 Example 2 Fig 5 Network bus resistor jumper RX ТX NBT NBT NBT Slave 2 Master Slave n Slave 1 Slave 2 Slave 1 RX ТX NBT NBT Master Slave n ATTENTION On a Modbus RTU network two bus terminators NBTs n...

Page 10: ...ck start disabled Input voltage mode 0 10 VDC Min setting of the Min speed trimmer Max setting of the Max speed trimmer Min setting of the Off level trimmer 3 Set the analog input signal to the maximum value of 10 VDC or 20 mA 4 The connected motor will run at maximum speed or minimum speed depending on the analog input mode ascending descending 5 If OFF level is enabled and descending analog inpu...

Page 11: ... switched on When Timer mode is selected the controller receives a pulse control signal from the remote control switch When Logic mode is selected the controller receives a pulse control signal from the Ai input In both modes Timer mode and Logic mode the pulse width is to be more than 30 ms otherwise the signal is filtered FRONT PANEL LED INDICATION When the green LED on the front cover Fig 10 gi...

Page 12: ...ximum output voltage 75 100 75 100 75 Us 100 Us 6 Minimum output voltage unsigned int Minimum output voltage 30 70 30 70 30 Us 70 Us 7 Enable off level unsigned int Enables off level 0 1 0 1 Disabled Enabled 8 Off level value unsigned int Off level value depending on the selected analog input type and ascending descending analog input mode 0 40 60 100 Ascending mode 0 400 0 200 Voltage 0 VDC 4 0 V...

Page 13: ...s settable Active only if holding register 7 is set to 1 0 1 0 0 1 Disabled Enabled 16 Off level value unsigned int Off level value Depends on the selected analog input type and ascending descending analog input mode Always settable Active only if holding register 7 is set to 1 0 40 60 100 0 Ascending mode 0 40 0 40 Voltage 0 VDC 4 0 VDC Current 0 mA 8 0 mA Descending mode 100 60 100 60 Voltage 10...

Page 14: ... 4 according to the selected operating mode The values are 0 for descending mode or 1 for ascending mode Input register 5 30005 shows the value of the maximum output voltage This input register is defined by holding register 13 or the hardware setting of the Max trimmer Fig 6 according to the selected operating mode The register values vary in range of 75 100 75 100 Us VAC Input register 6 30006 s...

Page 15: ... Single Register with address 1 and write the new address value 2 Connect only your unit to a master controller or PC application and send the command Write Single Register to address 0 Modbus broadcast address and write a new address value The next two registers 2 and 3 contain Modbus settings Changing these registers you change the communication settings The default Modbus settings are 19200 E 1...

Page 16: ...ly in timer mode and or logic mode The default value is 60 60 seconds The register values can vary from 0 to 200 0 200 seconds This setting is accessible only in Modbus mode The working time is equal to the sum of the kick start soft start duration and the time value of the operation timer When a working time expires only a remote control input or analog input can restart the unit The next holding...

Reviews: