Models MCD-1, 4, 8 & 16 Specifications
Size:
16.5” x 15” x 6.75” (42cm x 38.1cm x 17cm)
Weight:
Model MCD-1 - 30.4 lbs. (13.8 kg)
Model MCD-4 - 31.4 lbs. (14.2 kg)
Model MCD-8 - 33.8 lbs. (15.3 kg)
Model MCD-16 - 36.0 lbs. (16.3 kg)
Power:
120 or 240 Volts AC 50/60hz (41 Watts)
Temperature:
32 deg F – 125 deg F (0 deg C – 50 deg C)
Humidity:
0 – 95 % non-condensing
Atmospheric
Pressure:
75-106 Kpa
Equipment rated for indoor use only
Range:
0 – 1000 ppm Standard
Tube Length:
0 – 250 ft (0 – 76 m)
Sample
Areas:
Model MCD-1 - 1 Area
Model MCD-4 - 4 Areas
Model MCD-8 - 8 Areas
Model MCD-16 - 16 Areas
Trip Point:
Low Alarm 0 – 1000 ppm
Main Alarm 0 – 1000 ppm
High Alarm 0 – 1000 ppm
Horn Alarm Programmable to Low, Main or High
Leak Wait:
Varies from seven (7) seconds to three (3) minutes depending on
refrigerant concentration
Alarm
Output:
Low, Main, High and Horn alarm relays, each with four (4) form C
contacts rated 5 amps maximum
Analog
Output:
0 – 10 volt proportional to 0 – 1000 ppm
4-20 mA (optional)
Computer
Interface:
RS-485 (optional)