12
INSTALLATION
Unpack and Inspect Material
IR-SNIF-MCD Package:
The IR-SNIF-
MCD package contains the following
material:
1. IR-SNIF-MCD Refrigerant Monitor
2. Installation and Operation Manual
3. Hose barb fittings and coarse tube
end filters (one hose barb and filter
for each sample area and one each
for fresh air reference – two, five,
nine or seventeen of each are
provided)
4. CTS/Warranty form to be completed
and returned to Sentech
Optional Purchases:
The IR-SNIF-MCD
package may also contain the following
material:
1. Plastic FRPE tubing, ¼ inch OD for
sample tube
2. Combination Horn/Strobe alarm
3. Horn alarm
4. Strobe alarm
Other Required Material:
The following
material is required but not provided by
SenTech:
1. Primary power wiring
2. Wiring for connection to alarm
devices or other building systems
3. Relay contactors for building system
loads greater than 5 amps
4. ¼ inch tubing (if not purchased from
SenTech, or if copper tube is
required by local code)
If any material is missing, or appears to be
damaged, contact Sentech Corporation for
assistance.
Identify Location for Monitor, Sample
Points and Alarms
Monitor Location:
ASHRAE-15 specifies
that the refrigerant monitor is to be located
in the mechanical room. There are two
interpretations of this: the unit itself is to be
installed in the mechanical room; or the
sample point is to be located in the
mechanical room. Because the IR-SNIF-
MCD is an active air draw monitor, it can be
installed nearly anywhere in the vicinity of
the area to be monitored.
If local codes allow, the monitor can be
installed at the entrance to the mechanical
room, with the sample tube routed into the
mechanical room and the fresh air
reference routed to an appropriate location.
If the monitor is located outside the
mechanical room, a fitting should be
installed and an exhaust tube routed either
into mechanical room, or outdoors. If it is
routed outdoors, it must not be located near
the fresh air reference.
If local codes require the monitor to be
physically installed in the mechanical room,
it should be installed in the best location for
ease of use and routing of sample and
fresh air tubing. If the monitor is installed in
the same room as the sample pick-up-point,
no exhaust tube is required.
Caution: Liquid can affect the
performance of the monitor. Pick-
up-points must be protected from
exposure to water and other
liquids.
Sample Location:
Since the monitor
measures the concentration of refrigerant in
Summary of Contents for IR-SNIF-MC-1
Page 54: ...05 21 2008 ...