LZR -S600

®

Execute a teach-in.

RED

RED

RED

GREEN

GREEN

RED

ORANGE

ORANGE

ORANGE

ORANGE

ORANGE

BLUE

RED

BLUE

NO LED

NO LED

NO LED

NO LED

Verify or replace the batteries.

Verify the outside temperature where 
the sensor is installed. Eventually 
protect the sensor from sunlight using 
a cover.

Check the power supply voltage.

Wait a few seconds. If the LED remains 
ON, reset the power supply. If the LED 
turns on again, replace the sensor.

Check wiring.
The RED and BLUE cable have to be 
connected to the monitoring input.

Point the remote control towards the 
sensor, but with a slight angle. The RC 
should not be pointed in a right angle in 
front of the sensor.

Cut and restore power supply. No code 
is required to unlock during the first 
minute after powering.

Check cable and connexion.

Modify object size.

Check the size of the fields.

Walk out of the field and/or remove the 
object(s) from the field.

Activate the 3 red beams and check if 
the position of the sensor is correct. If 
not, adjust the hex screws.

Cut and restore power supply. The 
remote control session is accessible 
again during 30 minutes. 

Verify and clean the front screens.

Avoid highly reflective material in 
proximity to the sensor.

Verify the field size.

Check the position of the sensor.

Launch a new teach-in.

Check mounting side setting.

If there is no background, 
set the mounting side to value 3 to 5.

The sensor does not 
respond to the remote 
control.

The detection field LED 
remains GREEN.

The detection field LED 
remains RED.

Orange LED is flashing 
and the detection field 
LEDs are red. 

Orange LED is ON.

Only the BLUE LED is 
ON.

The batteries in the remote control 
are not installed properly or dead.

30 minutes after last use of the 
remote control, the sensor locks the 
access to the remote control 
session.

The remote control is badly pointed. 

The sensor does not 
unlock, even after 
entering the access code.

You have to enter a code or the 
wrong code was entered. (Maybe it 
was changed?).

No blue LED

There is no power.

The detection field is too small.

The object size is too small.

You or any other object moves or 
stays in the field.

The field is touching the floor, the 
wall or the door, which leads to 
detection.

The sensor is masked.

The sensor exceeds its temperature 
limits.

The power supply voltage is 
exceeding the acceptable limits.

Internal error

The monitoring input is not 
connected.

LED

SYMPTOMS

POSSIBLE CAUSES

CORRECTIVE ACTION

TROUBLESHOOTING

A reflective object is in close 
proximity to the sensor.

No background (reference point) is 
found.

7/8

Summary of Contents for LZR -S600

Page 1: ...Cable conduit LED signal Visible laser beams Laser sweep reception Laser sweep emission Tilt angle adjustments Main connector Front screens Caution Exposure to laser radiation Factory values See the...

Page 2: ...e device contains IR and visible red laser diodes IR laser CLASS 1 wavelength 905nm max output pulse power 75W Red laser CLASS 3R wavelength 650nm max output CW power 3mW Fasten the sensor firmly to a...

Page 3: ...sition the sensor correctly The grey area indicates the detection range Position the housing on the bracket Turn the sensor until the two triangles are face to face Position the bracket and fasten the...

Page 4: ...sponding mounting side with background Make sure you stay at a distance to avoid disturbances By choosing a value with background the sensor is protected against misuse The sensor memorizes the refere...

Page 5: ...IONS TEACH IN Field height Field width FIELD 2 FIELD 1 3 sec RED RED RED RED Before teach in you have 3 seconds to step out of the detection field 30 sec TEACH IN Wait for the sensor to learn its envi...

Page 6: ...TMENTS Relay configuration 1 Indoor 2 Outdoor LOW 3 Outdoor MEDIUM 4 Outdoor HIGH 0 size filter deactivated 1 5 cm 2 10 cm 3 15 cm 4 20 cm 1 Active NO 2 Passive NC 3 Passive NC 4 Active NO Passive NC...

Page 7: ...aterial in proximity to the sensor Verify the field size Check the position of the sensor Launch a new teach in Check mounting side setting If there is no background set the mounting side to value 3 t...

Page 8: ...typ 20 ms max 80 ms 2 electronic relays galvanic isolated polarity free 35 V DC 24 V AC 80 mA resistive t 5 ms t 5 ms ON OFF typ 30 0 7 V 20 mA 10 A 1 blue LED power on status 1 orange LED error stat...

Reviews: