FT 80 RLA Distance sensor - 068-13715 - 04.05.2009-03
Mounting and
operating instructions
32
Settings
The FT 80 RLA sensor can be configured as follows with functions 1 to 26 in setting mode (teach-in).
Button
S
Set button: Change / confirm a setting or set a switching point
T
Toggle button: Select a function (proceed to the next function)
Functions
* as long as the S button is pressed
No. LED Muster Description
“ZA” status indicator
Factory setting
1
Select Q
1
output mode.
On = Q
1
is a signal output
Off = Q
1
is not a signal output
On
2
Transfer of current meas. value as 1
st
switching point of Q
1.
signal output.
On* = Measured value valid
Off* = Measured value invalid
Half measuring
range
3
Scanning zone: Transfer of current meas.
value as 2
nd
switching point of Q
1
signal
output. Q
1
must be signal output (see
function no 1).
On = Measured value valid
Off = Measured value invalid
Off
4
N.C./N.O. change-over of switching
functions for Q
1
.
On = N.C.
Off = N.O.
N.O.
5
Q
2
output mode.
On = Q
2
is a signal output
Off = Q
2
displays good target
Off
6
Transfer of current meas. value as 1
st
switching point of Q
2
signal output.
Q
2
must be signal output (see function
no 5)
On* = Measured value valid
Off *= Measured value invalid
Good Target
7
Scanning zone: Transfer of current meas.
value as 2
nd
switching point of Q
2
signal
output. Q
2
must be signal output (see
function no 5).
On = Measured value valid
Off = Measured value invalid
Off
8
N.C./N.O. change-over of switching
functions for Q
2
.
On = N.C.
Off = N.O.
N.O.
9
Pulse stretching of Q
1
and Q
2
by 50 ms.
On = Pulse stretching on
Off = Pulse stretching off
Off