background image

ENGLISH

Pag. 3

1.  Introduction

The 1 relay card (STS1REL) for the SMART3 series gas detectors allows the detector to be 

provided with 1 voltage free changeover contact. 

2.  Technical specifications and layout

Contact rating: 50 mA at 24 Vdc; 100 mA at 12 Vdc

Figure 1)  Layout of the STS1REL card

3.  Assembly

Before inserting the STS1REL card, be sure the detector has been powered off. Insert the 

vertical plug-in card into the 10-pole connector, paying attention to leave the two left side 

poles free. Make sure the card has been fully plugged in.

Turn the side comprising the red LED towards the main terminal board, as shown in figure 2.

for the SMART3G’s series, in order to properly activate the STS1REL relay card it is manda-

tory to open the jumper JP5-6 on the detector’s main PCB (refer to the SMART3G’s detector 

manual).

IMPORTANT!

CCLLOOSSEEDD::  NNOORRM

MAALLLLYY  EENNEERRGGIIZZEEDD  RREELLAAYY  ((DDEEFFAAUULLTT))  

OOPPEENN::  NNOORRM

MAALLLLYY  DDEE--EENNEERRGGIIZZEEDD  RREELLAAYY

Jp4

Relay

Jp4

NNOORRM

MAALLLLYY  OOPPEENN  ((NNOO))  CCOONNTTAACCTT  IIFF  JJUUM

MPPEERR  BBEETTW

WEEEENN  

11

  AANNDD  

22

    

NNOORRM

MAALLLLYY  CCLLOOSSEEDD  ((NNCC))  CCOONNTTAACCTT  IIFF  JJUUM

MPPEERR  BBEETTW

WEEEENN  22    AANNDD  33    ((DDEEFFAAUULLTT))

Jp3

1

2

3

Jp3

LED: LIT WHEN THE RELAY IS ENERGIZED

1

2

3
1

2

3

Summary of Contents for STS1REL

Page 1: ...Manuale d istruzione Instruction Manual MT1071 rev 4 10 12 2020 2020 SENSITRON S R L All rights reserved www sensitron it Scheda a un rel per SMART3 One relay card for SMART3 STS1REL...

Page 2: ...for any additional information relative to use or repair QUESTO MANUALE DEVE ESSERE LETTO ATTENTAMENTE DATUTTI COLORO CHE HANNO O AVRANNO LA RESPONSABILITA DI INSTALLARE UTILIZZARE O DI PRESTARE UN S...

Page 3: ...Italiano English SUMMARY 1 Introduction 3 2 Technical specifications and layout 3 3 Assembly 3 SOMMARIO 1 Introduzione 1 2 Caratteristiche tecniche e layout 1 3 Montaggio 1...

Page 4: ...erso la morsettiera generale come indicato nella figura 2 Per i rivelatori della serie SMART3G per il corretto funzionamento della scheda opziona le STS1REL necessario aprire il jumper JP5 6 posiziona...

Page 5: ...cita contatto rel WD Fault e nessun allarme Modalit di attivazione del rel WD Fault e allarme 2 WD Fault e allarme 3 WD Fault e allarme 3 7 8 7 8 7 8 7 8 Nota Indipendentemente dalla configurazione de...

Page 6: ...l board as shown in figure 2 for the SMART3G s series in order to properly activate the STS1REL relay card it is manda tory to open the jumper JP5 6 on the detector s main PCB refer to the SMART3G s d...

Page 7: ...RD Smart 3 PCB Relay LED Output relay contact WD Fault and no alarm Relay activation mode WD Fault and alarm 2 WD Fault and alarm 3 WD Fault and alarm 3 7 8 7 8 7 8 7 8 Note During start up condition...

Page 8: ...actdetails SENSITRONs r l Viale della Repubblica 48 20007 Cornaredo MI Italy TEL 39 0293548155 FAX 39 0293548089 www sensitron it E mail sales sensitron it LEADER IN SIL2 SIL3 FIXED GAS DETECTION SYST...

Reviews: