Installation
2.6.1
Sizing the Grounding Electrode Conductors
AC Side
– The size of the AC grounding electrode conductor (GEC – AC) depends on the size of
the largest ungrounded conductor feeding the AC load center. One #8 AWG (8.4 mm
2
) copper
conductor will serve as an AC grounding electrode conductor (GEC – AC) for AC power conductors
smaller than and including #2 AWG (33.6 mm
2
) copper. See Table 2-5 for additional values.
Table 2-5, AC Grounding Electrode Conductor Sizing
Size of Largest Ungrounded
Conductor
Minimum Size of Grounding
Electrode Conductor
#2 AWG (33.6 mm
2
) or smaller
#8 AWG (8.4 mm
2
)
#1 to #1/0 AWG (42.4 to 53.5 mm
2
)
#6 AWG (13.3 mm
2
)
#2/0 or #3/0 AWG (67.4 to 85.0 mm
2
)
#4 AWG (21.1 mm
2
)
Over #3/0 AWG (85.0 mm
2
)
through 350 kcmil
#2 AWG (33.6 mm
2
)
DC Side
– To size the DC grounding electrode conductor, you must fi rst determine which one
of the following three methods will be used to connect the DC and AC grounding points in the
inverter’s two electrical systems to the common “earth” ground:
Method 1 (Figure 2-19)
: This method uses a separate grounding electrode for the DC system
and the AC system. In this method—since there are multiple connections to the DC grounding
electrode (GEC – DC)—the size of the DC grounding electrode conductor cannot be smaller than
the largest conductor in the DC system (usually the battery-to-inverter cable).
The DC grounding electrode (GE – DC) must be bonded to the AC grounding electrode (GE – AC)
to make a grounding electrode system. This bonding conductor (BC) cannot be smaller than the
largest grounding electrode conductor, either AC or DC.
Figure
2-19, Multiple Connections to DC Ground Rod (Method 1)
AC
DC Service
Panel
AC Service
Panel
DC Electrical System
AC Electrical System
Neutral
Positive
Negative
DC
Grounding
System
Negative
SBJ
GC
GEC-AC
EGC - AC
AC Ground
DC Ground
SBJ
EGC - DC
GC
Neutral
Hot
GEC-DC
GE
GE
GBB
GBB
Grounding Electrode
(DC side dedicated)
Grounding Electrode
(AC side dedicated)
MS Series Inverter/Charger
BC
Summary of Contents for Magnum Energy MS Series
Page 1: ...Pure Sine Wave Inverter Charger MS Series Owner s Manual...
Page 23: ...2016 Sensata Technologies Page 13 Installation Figure 2 5 MS Dimensions MS2000...
Page 43: ...2016 Sensata Technologies Page 33 Installation Figure 2 16 AC Wiring for MS2000 Models...
Page 44: ...Page 34 2016 Sensata Technologies Installation Figure 2 17 AC Wiring for MS2000 15B 20B Models...