Installation
Table 2-2, DC Wire Size For Increased Distance
Inverter
Model
Minimum Recommended DC Wire Size (one way)*
5 feet or less
(1.5 m or less)
5 to 10 feet
(1.5 m to 3.0 m)
10 to 15 feet
(3.0 m to 4.6 m)
In Conduit
In Free Air
In Conduit
In Free Air
In Conduit
In Free Air
MS2000
#4/0 AWG
(107.2 mm
2
)
#2/0 AWG
(67.4 mm
2
)
#4/0 AWG x2
(107.2 mm
2
)
#4/0 AWG
(107.2 mm
2
)
not
recommended
#4/0 AWG x2
(107.2 mm
2
)
MS2012
#4/0 AWG
(107.2 mm
2
)
#2/0 AWG
(67.4 mm
2
)
#4/0 AWG x2
(107.2 mm
2
)
#4/0 AWG
(107.2 mm
2
)
not
recommended
#4/0 AWG x2
(107.2 mm
2
)
MS2812
#4/0 AWG
(107.2 mm
2
)
#4/0 AWG
(107.2 mm
2
)
#4/0 AWG x2
(107.2 mm
2
)
#4/0 AWG x2
(107.2 mm
2
)
not
recommended
not
recommended
MS2024
#1 AWG
(42.4 mm
2
)
#4 AWG
(21.1 mm
2
)
#1/0 AWG
(53.5 mm
2
)
#2 AWG
(33.6 mm
2
)
#2/0 AWG
(67.4 mm
2
)
#1/0 AWG
(53.5 mm
2
)
MS4024
#4/0 AWG
(107.2 mm
2
)
#2/0 AWG
(67.4 mm
2
)
#4/0 AWG x2
(107.2 mm
2
)
#4/0 AWG
(107.2 mm
2
)
not
recommended
#4/0 AWG x2
(107.2 mm
2
)
MS4048
#1 AWG
(42.4 mm
2
)
#4 AWG
(21.1 mm
2
)
#1/0 AWG
(53.5 mm
2
)
#2 AWG
(33.6 mm
2
)
#2/0 AWG
(67.4 mm
2
)
#1/0 AWG
(53.5 mm
2
)
* Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F).
2.4.3
DC Cable Connections
Do not put anything between the battery cable ring lug and the battery post or the fl at metal part
of the inverter’s DC terminal. When connecting the battery cable to the battery post or inverter
DC terminal, the cable should be placed directly against the inverter terminal or battery post.
Incorrectly installed hardware causes a high resistance connection which could lead to poor inverter/
charger performance, and may melt the cable and terminal connections.
CAUTION:
The DC terminal and Flange/Kep nuts are made of stainless steel which have
a high likelihood of seizure. To help prevent the bolt and nut from seizing—causing the
bolts to strip or snap/break-off —the use of anti-seize lubricant is highly recommended.
Info:
If antioxidant grease or spray is used, apply it after all the connections have been
made and are properly tightened. A 1/2-inch wrench or socket is used to tighten the 5/16
SAE Flange/Kep nuts.
Refer to Figures 2-7 and 2-8 on the next page to connect the DC cables and to stack the hardware
correctly. Tighten the terminal connections from 10 to 12 ft lbf (13.6 to 16.3 N-m).
If a fuse is used as an overcurrent device, a Class-T type or equivalent is recommended. This
fuse type is rated for DC operation, can handle high short-circuit currents, and has a time delay
that allows for momentary current surges from the inverter without opening the fuse. However,
because the fuse can be energized from both directions, the NEC requires that it be installed in a
manner that the power must be disconnected on both ends of the fuse before servicing.
Use Table 2-1 to select the DC overcurrent device needed based on the recommended minimum
wire size for your particular inverter model (may not meet all local code or NEC requirements).
Summary of Contents for Magnum Energy MS Series
Page 1: ...Pure Sine Wave Inverter Charger MS Series Owner s Manual...
Page 23: ...2016 Sensata Technologies Page 13 Installation Figure 2 5 MS Dimensions MS2000...
Page 43: ...2016 Sensata Technologies Page 33 Installation Figure 2 16 AC Wiring for MS2000 Models...
Page 44: ...Page 34 2016 Sensata Technologies Installation Figure 2 17 AC Wiring for MS2000 15B 20B Models...