Installation
FRONT VIEW
~2"
~1"
0.375"
diameter
Cable
~¾”
(~2.54 cm)
(~5.1 cm)
(~1.9 cm)
SIDE VIEW
~½”
(~1.3 cm)
(~.95 cm)
Cable
Figure 2-9, Battery Temperature Sensor
2.4.5
Battery Temperature Sensor Installation and Wiring
The Battery Temperature Sensor (shown in Figure 2-9) provides the inverter with precise battery
temperature information to automatically adjust the ABSORB and FLOAT charge voltage set-points.
This allows the batteries to be correctly charged under extreme temperature changes.
If the temperature sensor is NOT installed and the batteries are subjected to large temperature
changes, the battery life may be shortened. The BTS cable may be extended—using a RJ11
connector (female to female) and a standard phone cable with RJ11 connectors—to a maximum
length of 40 feet (12 m). However, your inverter to battery cable length should not exceed the
recommended distance provided in Table 2-2.
To install the BTS:
1. Attach the ring terminal end of the Battery Temperature Sensor to the negative battery terminal;
see Figure 2-7 for proper connection to the battery terminal.
2. Route the sensor’s cable to the inverter following existing wire runs.
3. Connect the RJ11 connector end of the BTS cable to the yellow-labeled BTS port on the inverter
(Figure 1-1, Item 6).
Summary of Contents for Magnum Energy MS Series
Page 1: ...Pure Sine Wave Inverter Charger MS Series Owner s Manual...
Page 23: ...2016 Sensata Technologies Page 13 Installation Figure 2 5 MS Dimensions MS2000...
Page 43: ...2016 Sensata Technologies Page 33 Installation Figure 2 16 AC Wiring for MS2000 Models...
Page 44: ...Page 34 2016 Sensata Technologies Installation Figure 2 17 AC Wiring for MS2000 15B 20B Models...