Page 39
Troubleshooting
12NP Manual
LED Status Chart
Status LED Normal States
LED Color
LED State
Operating Conditions
Green
1 blink
Bulk Charge
Green
2 blinks
Accept Charge
Green
3 blinks
Float Charge
Green
4 blinks
Load Management Active
Green
5 blinks
Equalization
Green
6 blinks
.
Cold Charging
Amber
1 blink
Inverting
Status LED Fault States
LED Color
LED State
Fault State
None
Off
No Power to Unit or Internal Fault
Red or Amber
Constant On
Internal Fault
Red
1 blink
Inverter Low Battery Shutdown*
Red
2 blinks
Inverter Overload Shutdown
Red
3 blinks
Transformer High Temperature*
Red
4 blinks
MOSFET High Temperature*
Red
5 blinks
Battery Sensor Open or Shorted
Red
6 blinks
Inverter or Charger Disabled by CAN
Red
7 blinks
0 Amp Limit Set**
Red
9 blinks
Charger High Battery Temperature*
Red
10 blinks
Charger Off, Overload
Red
11 blinks
Reverse Polarity (Not Implemented in All Models)***
Red
12 blinks
Low Battery Temperature Shutdown
Amber
2 blinks
Charger Warm Battery*
Amber
3 blinks
High Battery Voltage*
Amber
4 blinks
System Overload, Reset Required****
Amber
5 blinks
Charger Off, Battery Shorted***
Table 12 LED Status Chart
* Faults will self-recover when the condition returns to normal range
** If the AC limit is set to 0 A, there will be no current available and the charger will not operate, but bypass will
still function. This fault will self-recover when the setting is changed to >0.
*** The inverter/charger must be sent back to the factory for evaluation.
**** Faults may be due to a short-circuited output or a low or weak DC voltage source.