Upright, Pendent, Recessed Pendent Sprinkler

   

Quick Response, Standard Coverage, 
Model FR-QR    K-Factor: 5.6 
SIN: SS2551, SS2552 

 

 

 

GENERAL DESCRIPTION 

 
The Model FR-QR 5.6 (80.6 LPM/bar

1/2

) K-factor, Upright, Pendent and Recessed Pendent Sprinklers are fusible link type 

automatic sprinklers. The Model FR-QR sprinklers are quick response standard coverage and are designed for use in light or 
ordinary hazard commercial occupancies. 
They are to be installed per NFPA 13 guidelines. 
The Model FR-QR Recessed Pendent Sprinkler is intended for use in areas with a finished ceiling, where applicable. This 
sprinkler can be used with our two-piece escutcheons to achieve the following results: 
A D1 Recessed Escutcheon (two-piece) provides a total adjustment of 1/2 inch (12.7 mm). 
A D2 Recessed Escutcheon (two-piece) provides a total adjustment of 3/4 inch (19.1 mm). 
 

WARNINGS 

The Model FR-QR must be installed and maintained in accordance with the rules stated herein as well as in 
compliance with the applicable standards of the National Fire Protection Association regulations and the standards of 
any other authorities having jurisdiction. 
In the event of this condition, consult the authorities having jurisdiction for guidance and approval. 
Failure to do so may impair the integrity of these devices. 
It is the responsibility of the installing contractor to provide a copy of this document to the owner or their 
representative, and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner. 
The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The 
installing contractor or sprinkler manufacturer should be contacted with any related questions. 

 
 

TECHNICAL DATA 

 

Approvals:

 c

UL

us

 Listed, FM Approved, Refer to TABLE A 

Sprinkler Identification Number (SIN): SS2551, SS2552, Refer to TABLE A 
Maximum Working Pressure: 175psi (12.1bar) 
Discharge Coefficient (Nominal K-Factor): K=5.6 GPM/psi

1/2

 (80.6 LPM/bar

1/2

Temperature Rating: Refer to TABLE A 
Finishes 

Sprinkler: Natural Brass, White Painted, Black Painted, Chrome Plated 
Recessed Escutcheon: Brass Plated, White Painted, Black Painted, Chrome Plated 

 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for FR-QR

Page 1: ...as well as in compliance with the applicable standards of the National Fire Protection Association regulations and the standards of any other authorities having jurisdiction In the event of this condi...

Page 2: ...Page 2 of 9 Document No U086951 Date Jan 11 2019 FIGURE 1 Model FR QR K5 6...

Page 3: ...s Quick Response Sprinklers 3 Listed by UL for use in Canada as Quick Response Sprinklers 4 Approved by FM as Quick Response Sprinklers OPERATION The sprinkler assemblies fusible link is comprised of...

Page 4: ...sition reaction forces resulting from sprinkler operation could alter its orientation and its water distribution pattern Obstruction to Water Distribution Locations of sprinklers must follow the obstr...

Page 5: ...t the position Installing Procedure Install Model FR QR sprinklers by the steps and figures shown below Use only D1 or D2 Recessed Escutcheons with Model FR QR Pendent sprinklers Use of any other rece...

Page 6: ...Page 6 of 9 Document No U086951 Date Jan 11 2019 FIGURE 3 UPRIGHT PENDENT and RECESSED PENDENT SPRINKLERS FIGURE 4 INSTALLATION CORRECT and INCORRECT FIGURE 5 INSTALLATION WRENCH...

Page 7: ...e 7 of 9 Document No U086951 Date Jan 11 2019 FIGURE 6 PROTECTOR REMOVAL FIGURE 7 INSTALLATION SOCKET A 1 2 drive ratchet not included is required for use with the Socket FR H FIGURE 8 PROTECTOR REMOV...

Page 8: ...preparation for maintenance of the fire protection system permission to close the main control valve must be obtained from the proper authorities and all affected parties by this action and must be i...

Page 9: ...and the regulations of any other authorities having jurisdiction The owner should direct any questions regarding the above rules and regulations to the installing contractors or the sprinkler manufac...

Reviews: