MI00597-0-EN

INSTALLATION MANUAL

2/4

CERTIFICATIONS

https://www.seneca.it/products/z8tc-si/doc/CE_declaration

https://www.seneca.it/products/z8tc-si-lab/doc/CE_declaration

POWER SUPPLY

Voltage: 10 ÷ 40Vdc; 19 ÷ 28Vac; 50-60 Hz; absorption: 0.6W max

ENVIRONMENTAL 

CONDITIONS

Operating temperature: -25°C ÷ +70°C.

Humidity: 30% ÷ 90% non condensing.  

Storage temperature: -30°C ÷ +85°C

Altitude: Up to 2000 m above sea level

Protection rating: IP20

ASSEMBLY

35mm DIN rail IEC EN60715

CONNECTIONS

4-way removable terminal block, 3.5mm pitch, 1.5 mm

cable section max

COMMUNICATION 

PORTS

IDC10 rear connector for IEC EN 60715 DIN bar, ModBUS-RTU, 1200÷115200 Baud

Micro USB on the front, ModBUS protocol, 2400 Baud

INSULATION

COMMUNICATION 

PORTS

RS485 on IDC10 connector

PROTOCOL

ModBUS- RTU

TC INPUTS

No. of channels: 8; Type of thermocouples: J, K, E, N, S, R, B, T, L (individually activated and configurable in pairs)

MODULE LAYOUT

SIGNALS VIA LED ON FRONT PANEL

17.5 mm

Dimensions:

 17.5 x 102.5 x 111 mm

Weight

:

 100 g

Container:

 PA6, black

11

1 mm

102.5 mm

LED

STATUS

LED meaning

PWR

ON

The device is powered correctly

FAIL

ON

Instrument in error state

RX

Flashing

Data receipt on port #1 RS485

TX

Flashing

Data transmission on port #1 RS485

TECHNICAL SPECIFICATIONS

N.B.: 

A delayed fuse with a maximum rating of 2.5 A must be installed in series with the power supply connection, near the module.

Power

Supply

TC4

TC5

TC6

TC7

TC8

TC3
TC2

TC1

Comm.

1500 V

ac

40 V

ac

RS485

Z-8TC-SI

Z-8TC-SI-LAB

Summary of Contents for Z-8TC-SI

Page 1: ...s during any operation PRELIMINARY WARNINGS The word WARNING preceded by the symbol indicates conditions or actions that put the user s safety at risk The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment The warranty shall become null and void in the event of improper use or tampering with the module or devices suppli...

Page 2: ...15200 Baud Micro USB on the front ModBUS protocol 2400 Baud INSULATION COMMUNICATION PORTS RS485 on IDC10 connector PROTOCOL ModBUS RTU TC INPUTS No of channels 8 Type of thermocouples J K E N S R B T L individually activated and configurable in pairs MODULE LAYOUT SIGNALS VIA LED ON FRONT PANEL 17 5 mm Dimensions 17 5 x 102 5 x 111 mm Weight 100 g Container PA6 black 111 mm 102 5 mm LED STATUS LE...

Page 3: ...1 stop bit FACTORY SETTINGS 1 2 3 4 5 6 7 8 KEY ON OFF SPAN mV 150mV IMPEDANCE 4MΩ ADC 24 bit TEMPERATURE DRIFT 100ppm K COLD JUNCTION ERROR 1 C TEST CURRENT 100nA CMRR 70dB 100ms DMRR 60 dB SUPPORTED INPUT SPECIFICATIONS SENSOR ACCURACY AT 23 C SOLUTION MEASURING RANGE STANDARD J 0 03 0 2 C 0 5µV 0 01 C 0 C 210 1200 C EN 60584 1 1997 K 0 03 0 2 C 0 5µV 0 02 C 0 C 200 1372 C EN 60584 1 1997 R 0 03...

Page 4: ...bjects that obstruct the ventilation slots Avoid mounting modules over heat generating equipment Installation in the bottom part of the electrical panel is recommended These are open type devices intended for installation in a final casing panel that offers mechanical protection and protection against the spread of fire 1 Install the modules in the DIN rail 120 max 2 Connect the remote modules usi...

Reviews: