ANALOGUE OUTPUT CONFIGURATION
10.2.18.
The analogue output is completely configurable passing 4 points: two of net weight and two of analogue
output:
Example:
We would like the analogue output to be 4 mA with a net weight of 0 Kg and 20 mA with a net weight of 10 Kg:
With net weighing
0 Kg
the output must be
4 mA
With net weighing
10 Kg
the output must be
20 mA
Between these two points the value is linear (for example at 5 Kg the output will be 12 mA).
STATION ADDRESS
10.2.19.
It represents the station address used in the Modbus RTU slave protocol available in the RS485 port.
BAUD RATE
10.2.20.
It selects the baud rate to be used in the communication from the RS485 port.
PARITY
10.2.21.
It sets whether the communication of the RS485 port must take place with or without even or odd parity.
DELAY IN REPLYING
10.2.22.
It introduces the delay to the Modbus response in number of characters.
SAMPLE WEIGHT
10.2.23.
It sets the weight of a single piece in technical units for the "piece weighing" mode. By setting the net weight of
a single element in this register, the device will be able to indicate the number of pieces present in the scales
according to the relation:
𝑁𝑁𝑟𝑟
𝑠𝑠𝑟𝑟𝑠𝑠𝑝𝑝𝑠𝑠𝑠𝑠
=
𝑁𝑁𝑠𝑠𝑟𝑟
𝑊𝑊𝑠𝑠𝑟𝑟𝑟𝑟ℎ𝑟𝑟
𝑂𝑂𝑛𝑛𝑠𝑠
𝑃𝑃𝑟𝑟𝑠𝑠𝑝𝑝𝑠𝑠
𝑊𝑊𝑠𝑠𝑟𝑟𝑟𝑟ℎ𝑟𝑟
AUTOMATIC TARE TRACKER
10.2.24.
It allows to set the automatic tare reset.
10.2.24.1.
TARE TRACKER
It allows you to enable or disable the automatic tare reset.
10.2.24.2.
ADC VALUE
It allows to set the number of ADC points within which to reset the tare automatically.
If after 5 seconds of stable weighing condition the ADC value of the net weight deviates by less than this value
then a new tare is acquired.