REGISTER
NAME
COMMENT
REGISTE
R TYPE R/W
DEFAUL
T VALUE
OR
START
VALUE
ADDRESS
(4xxxx)
OFFSET
ADDRES
S
ALARM
STATUS
Alarm status flag:
BIT 0 = Max Pre-Alarm
BIT 1 = Min Pre-Alarm
BIT 2 = Internal Window
Pre-Alarm
BIT 3 = External Window
Pre-Alarm
Bit 4..Bit 7 = Not Used
BIT 8 = Max Alarm
BIT 9 = Min Alarm
BIT 10 = Internal
Window Alarm
BIT 11 = External
Window Alarm
BIT 12..15 = Not Used
Unsigned
16 bits
R
0
40067
66
MODBUS
STATION
ADDRESS
Modbus RTU station
address
Unsigned
16 bits
RW*
1
40101
100
BAUD RATE
RS485 Port Baud rate
0 = 4800 baud
1 = 9600 baud
2 = 19200 baud
3 = 38400 baud
4 = 57600 baud
5 = 115200 baud
6 = 1200 baud
7 = 2400 baud
Unsigned
16 bits
RW*
3
40102
101
PARITY
Communication Parity
Bit
0 = None (8,N,1)
1 = Even (8,E,1)
2 = Odd (8,O,1)
Unsigned
16 bits
RW*
0
40103
102