User Manual
T201DCH50/100/300/600-MU
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
www.seneca.it
Doc. MI00546-EN
Rev.2
Page 16
REGISTER
NAME
COMMENT
REGISTE
R TYPE R/W
DEFAUL
T VALUE
OR
START
VALUE
ADDRESS
(4xxxx)
OFFSET
ADDRES
S
INTEGER
CURRENT
VALUE
[A X100]
[A X10]
(T201DCH600
A)
Current Measure Value
in signed integer
[A x100]
For example:
18534 = 185.34 A
-2500 = -25.00 A
[A x10] for 600A model
For example:
60000 = 600.0 A
Signed 16
Bits
R
-
40051
50
CURRENT
MIN
[A]
Minimum Current Value
(use register Command
for reset the value)
The value is set to 0 at
startup
Float32
R
-
40059
(LSW)
40060
(MSW)
58-59
CURRENT
MAX
[A]
Maximum Current Value
(use register Command
for reset the value)
The value is set to 0 at
startup
Float32
R
-
40061
(LSW)
40062
(MSW)
60-61
OUTPUT
VOLTAGE
[V]
Output Voltage
Float32
R
-
40063
(LSW)
40064
(MSW)
62-63
INVERSE
FLOAT
CURRENT
VALUE
[A]
Current Measure Value
in floating point MSW-
LSW
[A]
Copy of Float Current
Value
Registers with Inverse
(MSW-LSW) Floating
Point
Float32
R
-
40065
(MSW)
40066
(LSW)
64-65