User Manual
T201DCH50/100/300/600-MU
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
www.seneca.it
Doc. MI00546-EN
Rev.2
Page 15
5.6.
T201DCH-MU: MODBUS 4xxxx HOLDING REGISTERS TABLE (FUNCTION CODE 3)
REGISTER
NAME
COMMENT
REGISTE
R TYPE R/W
DEFAUL
T VALUE
OR
START
VALUE
ADDRESS
(4xxxx)
OFFSET
ADDRES
S
MACHINE ID
Module ID code
Unsigned
16 bits
R
-
40001
0
FIRMWARE
REVISION
Firmware Revision Code Unsigned
16 bits
R
-
40002
1
RESERVED
Reserved
Float32
R
-
40003
(LSW)
40004
(MSW)
2-3
RESERVED
Reserved
Unsigned
16 bits
R
-
40005
4
COMMAND
This register is used for
sending commands to
the device.
The following commands
are supported:
49600
Store configuration in
Flash
49568
Reset the Module
49920
Reset I max Value
49921
Reset I min Value
After the command is
executed the register will
return to 0 value
Unsigned
16 bits
R/W
0
40006
5
FLOAT
CURRENT
VALUE
[A]
Current Measure Value
in floating point LSW-
MSW
[A]
Float32
R
-
40049
(LSW)
40050
(MSW)
48-49