RETRANS_INT
Visualize the quantity to transmit normalised
0..+10000, scaled to min and MAX values set.
40217
R
Value of the quantity to transmit normalised
0..+10000, scaled to the minimum and maximum
threshlod set in registers MINOUT_FL (40020-
21) e MAXOUT_FL (40022-23) respectively.
0
: if the floating point value of the quantity to
transmit is less than MINOUT_FL (40020-21).
10000
: if the floating point value of the quantity to
transmit is equal to MAXOUT_FL (40022-23).
In the intermediate points has a linear behaviour.
The value of the register follows linearly the
quantity to transmit until maximum value set to
11000, saturating over this value.
Bit [15:0]
MI001458-E
ENGLISH - 16/16
RETRANSMITTED OUTPUT: FACTORY SETTINGS
the device is configured by default to retransmit on the analogue output the
THREE-PHASE POWER measured on a 4-wire connection (three phase +
neutral).
The parameters are as follows:
P.tot. W = 9000 = Out 4 .. 20 mA; I TA = 5 A; V = 600 Vac
This configuration allows you to get maximum power with external TA ratio 1:1
(WARNING: the external TA is always necessary because the instrument
performs the measurement of current through not isolated internal shunt).
Clearly the power is related to a voltage of 600 V measured between phase
and neutral, in the case of lower voltage, typically 230 VAC between phases
and neutral, the output will never reach the value of 20 mA and will stop at a
maximum power of 3450 W which corresponds to 10.13 mA.
Any change of the values described above, and in particular the re-scaling of
retransmitted output it should be done using the configuration software EASY
SETUP together with the selection of output type using the DIP-switches.