MI001458-E
ENGLISH - 11/16
00000000 (0x00) : 4800 Baud
00000001 (0x01) : 9600 Baud
00000010 (0x02) : 19200 Baud
00000011* (0x03) : 38400 Baud
00000100 (0x04) : 57600 Baud
00000101 (0x05) : 115200 Baud
00000110 (0x06) : 1200 Baud
00000111 (0x07) : 2400 Baud
VRMS_A_FL_MSW
VRMS_B_FL_MSW
VRMS_C_FL_MSW
VRMS_A_FL_LSW
VRMS_B_FL_LSW
VRMS_C_FL_LSW
Single phase or phase A Vrms measurement
(floating point, most significative word) in Volt
Phase B Vrms measurement (floating point,
most significative word) in Volt
Phase C Vrms measurement (floating point,
most significative word) in Volt
Single phase or phase A Vrms measurement
(floating point, least significative word) in Volt
R
R
R
R
R
R
40135
40137
40139
40136
40138
40140
RESET_ZERO
ENERGY
STATUS
Reset instrument and zero setting energy
Status Register
R/W
R
40131
40133
Bit [15:0]
-Writing 0x1234 resets(boots) instrument.
- W r i t i n g 0 x 1 0 0 0 , r e s e t s a c t i v e e n e r g y
accumulation in all three phases (unless ERR led
is blinking).
Bit 15
Bit [14:7]
Bit 6
Bit 5
Bit 4
Bit 3
Bit [2:0]
1
:
.
Error saving Active Energy value
Not Used.
1
:
Phase B and C are reverse-connected
1
:
Voltage on phase C is > 40 V therefore
measurements on phase C are correctly acquired.
1
:
Voltage on phase B is > 40 V therefore
measurements on phase B are correctly acquired.
1
:
Voltage on phase A is > 40 V therefore
measurements on phase A are correctly acquired.
Non utilizzati.
Bit [7:0]
Set the response delay time in characters that
represents the number of pauses of 6 characters
each to be entered between the end of the Rx
message and the start of the Tx message.
Default: 0
Phase B Vrms measurement (Floating point,
least significative word) in Volt
Phase C Vrms measurement (Floating point,
least significative word) in Volt