USER MANUAL – RTU-LP-ST
24
GSM Field Medium Value =1
GSM Field Maximum Value =1
Send Timestamp = 04 /May /2017 at 15:55
7.
ANALOG INPUTS LOG FTP FILE (FILE0)
The RTU can be configured for log the two Analog inputs with a minimum Log time of 30 seconds.
The Analog Inputs File0 Log file can only be sent to an FTP server, the file is a text file in a standard csv
format (comma-separated values).
The log can be sent in a report every N minutes (with N <= 1 minute).
Note that the log is sent N minutes after the modem is switched off.
For example if the log must be sent every 10 minutes we can obtain:
FIRST LOG SENT AT 12:00 -> COMMUNICATION TIME FOR SENDING THE LOG 1 MINUTE -> MODEM SWITCH
OFF AT 12:01
SECOND LOG SENT AT 12:01+10minutes= 12:11 -> TIME FOR SEND THE LOG 1 MINUTE -> MODEM SWITCH
OFF AT 12:12
THIRD LOG SENT AT 12:12+10minutes=12:22 -> TIME FOR SEND THE LOG 1 MINUTE -> MODEM SWITCH
OFF AT 12:23
…
A single file can contain a maximum of 64 Data Rows so more than one file report can be created (for
example sending a File0 Report every 120 minutes with analog inputs sampled at 30s will generate
120*2=240 Rows of data, so will be created 4 files).
The FTP file name is :
RTUNAMERTUCODE_YYYY-MM-DD_HH-MM_KKKK_File0.csv
Where:
RTUNAME: is the RTU Name configured with Easy RTU-LP Software
RTUCODE: is the numerical RTU code configured with Easy RTU-LP Software
YYYY-MM-DD_HH-MM: it’s the date/hour of the dispatch