USER MANUAL – RTU-LP-ST
19
Battery Voltage = 10.6V
Temperature = 22.4°C
GSM Field Minimum Value =1
GSM Field Medium Value =1
GSM Field Maximum Value =1
Send Timestamp = 04 /May /2017 at 15:55
6.
REAL TIME EVENTS
Real Time events can be configured for to be sent immediately afterwards the event, or to be
logged in a “FILE1” file.
When a real time event is configured to be sent immediately, it’s possible to use a SMS and/or a
FTP file.
Caution!
The RTU will send real time events only when there is a change state.
6.1.
REAL TIME EVENTS SMS
When an event is registered in RTU will switch ON the modem and can immediately send a SMS.
The SMS it’s of this type:
EV xx EVENT_LABEL D>abcd00ef 1> ±gggggg 2> ±hhhhh T: dddddddddd eeeeeeeeee ffffffffff gggggggggg
BAT:yy.yV TEMP:xx.xC CSQ Med,Max,Min / ddmmyyhhmm:RTUCODE
Where:
xx is the event number (see table)
EVENT NUMBER
DESCRIPTION
00
DIN1 : Switched to logic level 0
01
DIN2 : Switched to logic level 0
02
DIN3 : Switched to logic level 0