USER MANUAL – RTU-LP-ST
23
Where:
RTUNAME: is the RTU Name configured with Easy RTU-LP Software
RTUCODE: is the numerical RTU code configured with Easy RTU-LP Software
YYYY-MM-DD_HH-MM: it’s the date/hour of the event
KKKK: is a progressive alphanumerical code
A file name example is:
MRTU10001_2017-05-08_11-49_042B.csv
The FTP file content is the same of the SMS in text format:
For example:
EV 31 REBOOT D> 11110010 1> +1797 2> -2500 T: 0 3354 1144 0 BAT:10.6V TEMP:22.4C CSQ 1,1,1 /
0405171555:0001
This means:
Event 31 = RTU RESET
Text Label for Event 31 = “REBOOT”
In1=In2=in3=in4 = High
Out1 = Set
Out2 = Reset
Analog 1 = 17.97%
Analog 2 = -25.00%
Totalizer1 = 0
Totalizer2 = 3354
Totalizer3 = 1144
Totalizer4 = 0
Battery Voltage = 10.6V
Temperature = 22.4°C
GSM Field Minimum Value =1