SP PRO Generic AC Coupling
Technical Bulletin
TB0006
Revision
01
– 2 of 7
System Requirements
To successfully install a SP PRO generic system, there are particular system requirements that
need to be met.
This installation document is applicable to SP PRO series I and II.
Combined maximum AC output of all the connected generic inverters must not exceed
the continuous SP PRO output power rating.
Battery bank must be sized to suit the SP PRO model and the combined maximum AC
Output power of the generic inverters.
SP PRO must have appropriate firmware version installed (Rev 7.0 and above).
SP PRO generic AC coupling is only suitable for grid connected systems.
SP PRO generic AC coupling cannot control any grid export limits.
The Grid Disconnect function in the Solar Hybrid Control should not be used.
SP
PRO
MODEL AND TOTAL
G
ENERIC
AC
OUTPUT
The total AC output of the Generic inverters must not be greater than the nominal capacity of
the SP PRO.
SP PRO Model
Combined maximum KACO AC
Output power
SPMC240
3 kW
SPMC241
4.5 kW
SPMC481
5 kW
SPMC482
7.5 kW
SPMC1201
7.5 kW
SPLC1202
20 kW
Table 1: Maximum Generic AC output per SP PRO model