SP PRO Generic AC Coupling
Technical Bulletin
TB0006
Revision
01
– 6 of 7
C
ONFIGURATION
–
A
DDITIONAL
S
ETTINGS
The settings detailed here are only the additional settings required to enable Generic AC
Coupling. The remainder of systems settings are not covered in this document.
The SP PRO
must
have the Generic settings configured in the SP PRO
before
any of the
generic inverters are energised. The AC coupled failsafe system in the SP PRO is only enabled
when the correct configuration has been programmed into the SP PRO.
SP
LINK
–
CONFIGURATION
SETTINGS
–
SYSTEM
The additional system settings required are detailed and shown below.
Enable Generic AC Coupling
SP LINK - Configuration Settings – System tab
Grid Export Limit and AC source Power settings
Set the AC Source Power (in Configuration Settings – Quick Start) to a value that is higher than
the total maximum power output of the connected generic grid tie inverters
If any of the Solar Hybrid Control - Priority (in Configuration Settings) Schedules are Enabled
then ensure that ALL of the used Grid Export Limit settings have been set to a value that is
higher than the total maximum power output of the connected generic grid tie inverters.
Additionally it is recommended setting all of the Grid Disconnect settings to Disabled (default
setting).
The SP PRO cannot control the output power of the generic AC grid tie inverters therefore
cannot control these functions.