Specifications

Compliance

ISO 9001:2008 Certified

General 

AC Current Inputs (Channels I1, I2, I3)

1 A nominal:

3 A continuous, linear to 20 A 

symmetrical; 100 A for 1 s

Burden:

0.13 VA @ 1 A
1.31 VA @ 3 A

Sensitive Earth Fault (SEF) Channel IN Current Input

0.05 A nominal:

1.5 A continuous, linear to 1.5 A 

symmetrical; 20 A for 1 s

Burden:

0.0004 VA @ 0.05 A, 0.36 VA @ 1.5 A

AC Voltage Inputs

300 V

L-N

 continuous, (connect any voltage up to 300 Vac). 600 Vac for 

10 s.

Burden:

0.03 VA @ 67 V
0.06 VA @ 120 V
0.80 VA @ 300 V

Power Supply

Rated Range:

85–264 Vac; 100–350 Vdc

Frequency Range:

40.1–65 Hz

Burden:

<30 VA

12 V Radio Supply

11–14 Vdc, 6 W continuous, 13 W for 1 s

Output Contacts (Except Trip and Close)

Make:

30 A per IEEE C37.90-1989

Carry:

6 A continuous carry at 70°C
4 A continuous carry at 85°C

1 s Rating:

100 A

MOV Protection:

270 Vac / 360 Vdc; 40 J

Pickup Time:

< 5 ms

Breaking Capacity (10000 operations, L/R = 40 ms):

24 V

0.75 A

48 V

0.50 A

125 V

0.30 A

250 V

0.20 A

Cyclic Capacity (2.5 cycle/second, L/R = 40 ms):

24 V

0.75 A

48 V

0.50 A

125 V

0.30 A

250 V

0.20 A

Note: Per IEC 60255-0-20:1974, using the simplified method of 

assessment.

Trip and Close Outputs

3 A continuous @ –40° to 40° C, 1 min @ 85°C

Make and Carry:

5 A for 0.2 s @ 1 s intervals

Optoisolated Inputs

DC Range

24 Vdc:

Pickup 15.0–30 Vdc

AC Range

24 Vdc:

Pickup 12.8–30 Vdc

Note

Optoisolated inputs draw approximately 4 mA of current. All 

current ratings are at nominal input voltages.

Frequency and Rotation

System Frequency:

50 or 60 Hz

Phase Rotation:

ABC or ACB

Frequency Tracking 

Range:

40.1–65 Hz

Note: Voltage connected to V1 required for frequency tracking.

Communications Ports

EIA-232:

2 Side

EIA-485 (optional):

1 Side, 2100 Vdc of isolation

Baud Rate: 

300–38400 baud

Time-Code Input

Recloser control accepts demodulated IRIG-B time-code input at Port 

1 (optional) and Port 2. Do not connect the time-code input into both 
Port 1 and Port 2 at the same time. Recloser control time is 
synchronized to within 

±

5 ms of time-source input.

Operating Temperature

Relay Module:

–40° to +85°C (–40° to +185°F)

Batteries:

–40° to +60°C (–40° to +140°F)

Entire SEL-351R Falcon 

Unit:

–40° to +50°C (–40° to +122°F)

Note: LCD contrast impaired for temperatures below – 20°C (–4

°

F). 

The entire SEL-351R Falcon unit was operation tested up to +70°C 
(+158°F). The 20°C (36°F) difference between the +50°C rating and 
+70°C allows for temperature rise due to sunlight.

Weight

16.7 kg (37 lbs) including batteries

Battery Specifications

Normal Capacity:

8.0 amp-hours at +25°C (+77°F)

Run Time:

20 hours at +25°C (+77°F)
8 hours at –40°C (–40°F)

Estimated Life:

4 years at +25°C (+77°F)
8 months at +60°C (+140°F)

Recharge Time:

55 hours at +25°C (+77°F)

Type Tests

Environmental Test

Cold:

IEC 60068-2-1:1990

[EN 60068-2-1:1993]
Test Ad: 16 hours at –40°C

Damp Heat Cyclic:

IEC 60068-2-30:1980

Test Db; 55

°

C, 12 + 12-hour cycles, 

95% humidity

Dry Heat:

IEC 60068-2-2:1974

[EN 60068-2-2:1993]
Test Bd: Dry heat, 16 hours at +85°C

Dielectric Strength and Impulse Tests

Dielectric:

IEC 60255-5:1977

IEEE C37.90-1989
2500 Vac on analogs, contact inputs, 

and contact outputs except Trip and 
Close; 3100 Vdc on power supply for 
10 s; 2200 Vdc on EIA-485 
communications port

Summary of Contents for SEL-351R Falcon

Page 1: ...BITS communi cations speeds protection and improves security Customize controls by using enhanced SELOGIC control equations for improved system operation Configurable front panel control labels simpl...

Page 2: ...ose interval The reset times are set separately for reset timing for an auto reclose and reset timing for a manual remote close from lockout Traditionally the reset time for a manual remote close from...

Page 3: ...y inverse class C extremely inverse long time inverse short time inverse Programmable curves user designed Four 4 programmable curves Optional 3 Phase Voltage connect to voltage channels V1 V2 and V3...

Page 4: ...er wear monitor measures unfiltered ac current at the time of trip and the number of close to open operations as a means of monitoring this wear Every time the recloser trips the recloser control reco...

Page 5: ...27 IRIG B SERIAL PORT 1 1 2 3 4 5 N C 7 8 SERIAL PORT 2 SERIAL PORT 3 OUT102 OUT101 OUT104 OUT103 OUT107 N C N C IN101 ALARM IN103 IN102 N C N C IN104 _ RECLOSER CONTROL I1 Z01 I2 Z02 I3 Z03 IN Z04 12...

Page 6: ...ttings Create Application Designs that include the most commonly used relay features and settings for your system see Figure 6 and watch commissioning times drop drastically Figure 6 Example Applicati...

Page 7: ...ress for 3 sec AUX 1 AUX 2 WAKE UP CLOSED RECLOSER OPEN RECLOSER TRIP CLOSE C B A LOCKOUT CYCLE CURVE FAST TAG HOT LINE PROBLEM BATTERY SUPPLY AC CURRENT HIGH 81 G SEF RESET A01 A04 A03 A02 A07 A06 A0...

Page 8: ...CLE CURVE FAST TAG HOT LINE PROBLEM BATTERY SUPPLY AC CURRENT HIGH 81 G SEF RESET A01 A04 A03 A02 A07 A06 A05 A08 A11 A10 A09 A14 A13 A12 A23 A16 A15 A17 A18 A22 A20 A19 A21 A26 A25 A24 A28 A27 IRIG B...

Page 9: ...digital quantities having a logical value of either 0 or 1 The terms assert or asserted refer to a Relay Word bit that has a value of 1 or is changing from 0 to 1 The terms deassert or deasserted refe...

Page 10: ...ry monitor charger the SEL 351R Falcon can monitor battery voltage The SEL 351R Falcon puts itself to sleep if voltage falls to a user set threshold or if a user set timer times out after an extended...

Page 11: ...n change most functions by programming to meet system requirements see Table 4 Use the optional configurable labels to customize the targets and control pushbuttons to best meet operational needs r Se...

Page 12: ...le CYCLE The control is actively in the trip reclose cycle mode LOCKOUT All reclose attempts were unsuccessful A B C a A B or C phase involved in fault G Ground involved in fault SEF Sensitive earth f...

Page 13: ...ol via serial communications These values shall be available for use in control logic Secure Communications The recloser control shall include an optional accessory for converting an EIA 232 serial po...

Page 14: ...tored Close Circuit Points Monitored Trip Circuit Points B D C A E F IRIG B 1 2 3 4 5 N C 7 8 FRONT PANEL OPERATOR CONTROLS 28 Vdc 24 Vdc 24 Vdc or 36 Vdc 12 Vdc FRONT PANEL TARGET LEDS AC SUPPLY CONT...

Page 15: ...Schweitzer Engineering Laboratories Inc SEL 351R Falcon Data Sheet 15 Relay Mounting Figure 16 SEL 351R Falcon Lift To Open Enclosure Dimensions and Mounting...

Page 16: ...SEL 351R Falcon Data Sheet Schweitzer Engineering Laboratories Inc 16 Figure 17 SEL 351R Falcon Swing Open Enclosure Dimensions and Mounting...

Page 17: ...ages Frequency and Rotation System Frequency 50 or 60 Hz Phase Rotation ABC or ACB Frequency Tracking Range 40 1 65 Hz Note Voltage connected to V1 required for frequency tracking Communications Ports...

Page 18: ...ow pass analog filtering Net filtering analog plus digital rejects dc and all harmonics greater than the fundamental Protection and Control Processing Four times per power system cycle Battery Monitor...

Page 19: ...20 C and at nominal system frequency unless noted otherwise Voltages VA VB VC VS 3V0 V1 V2 0 2 67 300 0 V wye connected Currents IA IB IC 1 A nominal 3 mA 0 1 0 1 20 A Temperature Coefficient 0 0002...

Page 20: ...laws in its products including without lim itation software firmware and documentation The information in this document is provided for informational use only and is subject to change without notice...

Reviews: