RKP01M0000SE 033955 290120
26/36
┌─────────────────────────────────────┐
│ MINIMUM IGNITION BURNER 1 │
│—————————————————————————————————————│
│ Data │ Adjustment range │ Default │
│——————│————————————————————│—————————│
│ tb1 │ OFF 1 .. 250 sec. │ 60 sec. │
└─────────────────────────────────────┘
To disable this function, set the parameter to "
OFF
".
┌─────────────────────────────────────┐
│ MINIMUM EXTINCTION BURNER 1 │
│—————————————————————————————————————│
│ Data │ Adjustment range │ Default │
│——————│————————————————————│—————————│
│ tO1 │ OFF 1 .. 250 sec. │ 60 sec. │
└─────────────────────────────────────┘
To disable this function, set the parameter to "
OFF
".
┌─────────────────────────────────────┐
│ MINIMUM IGNITION BURNER 2 │
│—————————————————————————————————————│
│ Data │ Adjustment range │ Default │
│——————│————————————————————│—————————│
│ tb2 │ OFF 1 .. 250 sec. │ 60 sec. │
└─────────────────────────────────────┘
Note: It is not possible to set the value of tb2 to a value
higher than the value of tb1, because the value of tb2 is
limited to the value of tb1.
If you want to increase the value of tb2, you must
increase the value of tb1 first, according to the relation:
tb2 ≤ tb1.
To disable this function, set the parameter to "
OFF
".
┌─────────────────────────────────────┐
│ MINIMUM EXTINCTION BURNER 2 │
│—————————————————————————————————————│
│ Data │ Adjustment range │ Default │
│——————│————————————————————│—————————│
│ tO2 │ OFF 1 .. 250 sec. │ 60 sec. │
└─────────────────────────────────────┘
Note: It is not possible to set the value of to2 to a value
lower than the value of to1, because the value of tb2 is
limited to the value of to1.
If you want to decrease the value of to2, you must
decrease the value of to1 first, according to the relation:
to2 ≥ to1.
To disable this function, set the parameter to "
OFF
".
┌─────────────────────────────────────┐
│ ADJUSTMENT ON INTERNAL │
│ CHRONOTHERMOSTAT (INt) OR │
│ ON EXTERNAL CONTACT (EHt) │
│—————————————————————————————————————│
│ Data │ Adjustment range │ Default │
│——————│————————————————————│—————————│
│ PRI │ INT .. EHt │ INt │
└─────────────────────────────────────┘
Note: Setting the parameter to "EXT", external contact,
will make the icon "
h
EXT" light up on the display,
whereas setting the parameter to "INT", adjustment
according to the program inside the unit, will make the
icon "
h
INT" light up on the display.
"
P3 OAF
"
SETTING ANTI-FREEZE TEMPERATURE
This parameter allows you to set the anti-freeze
temperature to protect the system if the supply water
temperature drops below the value set.
To disable this function, set the parameter to "
OFF
".
┌──────────────────────────────────────┐
│AFTER SELECTING THE PARAMETER 'P3 OAF'│
│ PRESS THE ' ' KEY. │
│ THE ELEMENT ‘TAF' WILL BE DISPLAYED; │
│ THEN PRESS THE ' 'KEY AGAIN; │
│ 'TAF' WILL FLASH ON THE DISPLAY. │
│ │
└──────────────────────────────────────┘
┌──────────────────────────────────────┐
│ SET THE DESIRED VALUE │
│ BY USING THE ARROWS '▼' AND '▲'. │
└──────────────────────────────────────┘
┌──────────────────────────────────────┐
│ PRESS THE ' ' KEY TO CONFIRM │
│ THE SETTINGS OR PRESS THE ’esc’ KEY │
│ TO CANCEL. │
│ │
└──────────────────────────────────────┘
┌─────────────────────────────────────┐
│ ANTI-FREEZE TEMPERATURE │
│—————————————————————————————————————│
│ Data │ Adjustment range │ Default │
│——————│————————————————————│—————————│
│ TAF │ OFF 1 .. 40 °C │ 5 °C │
└─────────────────────────────────────┘
To disable this function, set the parameter to "
OFF
".