⑫
Motion Frequency Display
The obstacle sensing function upon descent is set up by the dip switch.
In case of not needing the function, change the sensing power over to “OFF”.
Upon shipping the sensing power is set up to “ON”.
⑨
Obstacle Sensing Function upon Descent
When the sensing power upon descent is set up to "ON", you can adjust the descending
load sensitivity with the rotary switch.
Descending load sensitivity is set up to “6” at the time of shipping.
Adjust the sensitivity according to the situation of site where the shutter is installed.
Load sensitivity setting
0 1 2 3 4 5 6 7 8 9
Descending load sensitivity
Light
Heavy
The obstacle sensing function upon ascent is set up by the dip switch.
In case of not needing the function, change the sensing power over to
“
OFF
”
.
Upon shipping the sensing power is set up to
“
ON
”
.
The load sensitivity upon ascent is a fixed value.
⑩
Obstacle Sensing Function upon Ascent
When upper limit output is needed, change setting over to “Upper limit”.
When lower limit output is needed, change setting over to “Lower limit”.
Setting is adjusted to “Upper limit” at the time of delivery regardless of the specification
of upper- or lower-limit output.
⑪
Upper- and Lower- Limit Output Changeover
(for only specification accompanying upper- and lower-limit output)
This LED shows the motion frequency of the operator.
The LED lights up when the motion frequency exceeds 10,000 times in opening & closing.
Motion frequency display
LED
P6
Sensing power
“
ON
”
Sensing power
“
OFF
”
Sensing power
“
ON
”
Sensing power
“
OFF
”
Upper limit output
Lower limit output