TB MRM3 07.01 E
43
Protection Parameters (Contin.)
Unit
I
IE
Default set-
ting
Actual set-
ting
LED
Function
Set1/Set2
Set1 Set2
I>> + Start
Pick-up value for the phase short-circuit element at
start
x I
N
X
X
0.50
I>>
Pick-up value for the phase short-circuit element in
operation
x I
N
X
X
0.50
I>> + t>
Tripping time of the phase short-circuit element
s
X
X
0.04
I2>
Pick-up value of the load unbalance element
x I
N
X
X
0.020
I2> + CHAR
Trip characterist.of the load unbalance element
X
X
DEFT
I2> + t>
Tripping time of the unbalanced load element
s
X
X
1.0
I2>+CHAR + t> Reset mode for the load unbalance element
X
X
0s
I
E
>
Pick-up value of the earth fault element
(s)
X
0.010
I
E
> + CHAR
Trip characteristic earth fault element
X
DEFT
I
E
>+ t>
Tripping time (factor) earth fault element
(s)
X
0.04
I
E
>+ CHAR + t> Reset mode earth fault element
X
0s
CB + t>
Tripping time CB failure protection
s
X
X
EXIT
Trip + t>
Tripping time external trip
s
X
X
0.10
Block + Trip
Trip blocking at excessive phase current
x I
N
X
X
EXIT
Start parameters
Funktion
Unit
I
IE
Default set-
ting
Actual set-
ting
LED
Function
Set1/Set2
Set1 Set2
No.+Start
Duration of a start cycle
min.
X
X
30
No.
Number of starts per cycle
X
X
10
No.+Start+t>
Start blocking time
min
X
X
30
Start + t>
Max. start time t
s
X
X
EXIT
0 + I> + t>
Time of START recognition or MOTOR RUNNING
s
X
X
0.20
0 + I< + t>
Stopping time
s
X
X
0.50
Parameters for the fault recorder
LED
Function
I
IE
Default
Actual
Unit
setting
setting
FR
Number of recordings
4
FR
Storage of the recording at the event
TRIP
FR
Time period prior to the trigger impulse
s
0.05
Interface parameters
LED
Function
I
IE
Default set-
ting
Actual setting
RS
Slave Address of the serail interface
X
1
RS*
Baud rate of the serial interface
X
9600
RS*
Parity check of the serial interface
X
even
*only with Modbus Protocol