20
TB MRM3 07.01 E
5.9
Additional Functions
5.9.1 Blocking of the Protective Functions
Blocking of the protective functions
After voltage has been applied to blocking input
D8/E8, the intended reaction for each of the protec-
tive functions can be defined individually. (Observe
voltage adjustment !) See chapter 3.1.4
Setting
Effect when voltage has been applied
to the blocking input
PR_B
Complete blocking of the protective ele-
ment. Activation and trip are suppressed.
TR_B
Blocking of trip elements.
The individual protective elements are
activated and this is signalled accord-
ingly, but there is no tripping.
BLOC
Complete blocking of the protective ele-
ment. Activation and tripping are sup-
pressed. This is displayed if it is not dif-
ferentiated between PR_B and TR_B in a
parameter.
NO_B
No blocking.
This element operates normal, it is not
blocked
Table 5.3: Adjustment Possibilities
Setting of parameters should be done as follows:
•
To come to the blocking menu push-buttons
<ENTER> and <TRIP> are to be pressed at the
same time. The function being set is indicated by
LEDs.
•
If necessary the blocking function can be changed
with <+> or <-> and saved with <ENTER>
Perhaps a password has to be entered.
•
Proceed to the next function with
<SELECT/RESET>
•
After selection of the last blocking function settings
for the 2
nd
parameter set can follow.
•
For allocating the RESET function press push-button
<SELECT/RESET> again. (See next chapter).
Symbol
Protective Function
Default
Setting
Possible Settings
LED/Colour
ϑ
>
Overload warning element
NO_B
NO_B ; BLOC
ϑ
> red
I
B
>
Overload element
NO_B
NO_B ; PR_B ; TR_B
I
B
>
green
I<
Undercurrent element
NO_B
NO_B ; PR_B ; TR_B
I< red
I>
Overcurrent element
NO_B
NO_B ; PR_B ; TR_B
I> red
I>> Start Short-circuit element at start-up
BLOC
NO_B ; BLOC
I>> red/Start green
I>>
Short-circuit element
PR_B
NO_B ; PR_B ; TR_B
I>> red
I2>
Load unbalance element
NO_B
NO_B ; PR_B ; TR_B
I2> red
I
E
>
Earth current element
NO_B
NO_B ; PR_B ; TR_B
I
E
> red
tCBFP
CB failure protection
NO_B
NO_B ; BLOC
CB green
Trip
External trip
NO_B
NO_B ; BLOC
Trip red
Table 5.4: Default Setting of the Blocking Functions