30
TB MRU3-2 12.00 E
7.3
Setting ranges and steps
Function
Para-
meter
Setting range
Step
Pickup tolerance
Transformer ratio U
prim
/U
sek
(sek) 1.01...6500
0.01; 0.02; 0.05; 0.1;
0.2; 0.5; 1.0; 2.0; 5.0;
10; 20; 50
Switch group
D/Y
D = DELT/Y = Y
Rated frequency
f
N
f = 50 / f = 60 / v = 50 / v = 60
LED blinking at
pick-up
FLSH/NOFL
Parameter
switch/ext.
Triggering for
the fault re-
corder
P2|2
SET1/SET2/B_S2/R_S2/B_FR/R_FR/
S2FR
1/3-phase
tripping
1/3
U<>1; U<>3
U<
U<; U<<
U1<
t
U<
; t
U<<
;
t
U1<
U
N
= 100 V:
2...200 V (EXIT)
U
N
= 230 V:
2...460 V (EXIT)
U
N
= 400 V:
4...800 V (EXIT)
0.04...50 s (EXIT)
1 V
1 V
2 V
0.01; 0.02; 0.05; 0.1;
0.2; 0.5; 1.0; 2.0 s
±
1% of set value or
<0,3% U
N
±
1% oder
±
15 ms
U>
U>,
U>>,
U1>,
t
U>
, t
U1>
,
t
U1>
U
N
= 100 V:
2...200 V (EXIT)
U
N
= 230 V:
2...460 V (EXIT)
U
N
= 400 V:
4...800 V (EXIT)
0,04...50 s (EXIT)
1 V
1 V
2 V
0.01; 0.02; 0.05; 0.1;
0.2; 0.5; 1.0; 2.0 s
±
1% of set value or
<0.3% U
N
±
1% or
±
15 ms
U>
U
2>
, U
0>
t
U2>
, t
U0>
U
N
= 100 V:
2...100 V (EXIT)
U
N
= 230 V:
2...230 V (EXIT)
U
N
= 400 V:
4...400 V (EXIT)
0.04...50 s (EXIT)
1 V
1 V
2 V
0.01; 0.02; 0.05; 0.1;
0.2; 0.5; 1.0; 2.0 s
±
1% of set value or
<0,3% U
N
±
1% or
±
15 ms
7.3.1
Interface parameter
Function
Parameter
Modbus-Protocol
RS485 Open Data Protocol
RS
Slave-Adresse
1 - 32
1 - 32
RS
Baud-Rate*
1200, 2400, 4800, 9600
9600 (fixed)
RS
Parity*
even, odd, no
„even Parity“ (fixed)
* only Modbus Protocol