TB MRU3-2 12.00 E
23
5.9.2
Reset
All relays have the following three possibilities to reset
the display of the unit as well as the output relay at
jumper position J3=ON.
Manual Reset
•
Pressing the push button <SELECT/RESET> for some
time (about 3 s)
Electrical Reset
•
Through applying auxiliary voltage to C8/D8
Software Reset
•
The software reset has the same effect as the
<SELECT/RESET> push button (see also communica-
tion protocol of RS485 interface)
The display can only be reset when the pickup is not
present anymore (otherwise "TRIP" remains in display).
During resetting of the display the parameters are not
affected.
5.9.3
Erasure of fault storage
To delete the trip store, the push button combination
<SELECT/RESET> and <->, has to be pressed for
about 3s. The display shows “wait”.
Relay function
Output relays
Display-
Corres-
ponding
1
2
3
4
Indication
LED
U<
Alarm
_ _ _ _
U<;
green
tU<
Tripping
X
1 _ _ _
tU< red
U<<
Alarm
_ _ _ _
U<< green
tU<<
Tripping
X
1 _ _ _
tU<< red
U>
Alarm
_ _ _ _
U> green
tU>
Tripping
X
1 _ _ _
tU> red
U>>
Alarm
_ _ _ _
U>> green
tU>>
Tripping
X
1 _ _ _
tU>> red
U1<
Alarm
_ _ _ _
U1< green
tU1<
Tripping
X
_ 2 _ _
tU1< red
U1>
Alarm
_ _ _ _
U1> green
tU1>
Tripping
X
_ 2 _ _
tU1> red
U2>
Alarm
_ _ _ _
U2> green
tU2>
Tripping
X
_ _ 3 _
tU2> red
U0>
Alarm
_ _ _ _
U0> green
tU0>
Tripping
X
_ _ _ 4
tU0> red
Table 5.4: Example of assignment matrix of the output relay (defaults settings)