background image

10 

TD_MRI1-IU_05.04_GB 

5.2.10   Blocking the protection functions 
 

  and assignment of the output  

  

relays 

 

Blocking the protection functions: 

The blocking function of the 

MRI1-IU

    can be set ac-

cording to requirement. By applying the aux. voltage 
to D8/E8, the functions chosen by the user are 
blocked. Setting of the parameter should be done as 
follows: 

• 

When pressing push buttons <ENTER> and <TRIP> 
at the same time, message "BLOC" is displayed (i.e. 
the respective function is blocked) or "NO_B"  
(i.e. the respective function is not blocked). The LED 
allocated to the first protection function I> lights red. 

• 

By pressing push buttons <+> <-> the value dis-
played can be changed. 

• 

The changed value is stored by pressing <ENTER> 
and entering the password. 

• 

By pressing the <SELECT/RESET> push button, any 
further protection function which can be blocked is 
displayed. 

• 

Thereafter the blocking menu is left by pressing 
<SELECT/RESET> again. 

 

Function  

Display  LED/Colour 

I> Overcurrent 

 

(Low set) 

NO_B I> 

yellow 

I>> Overcurrent 

 

(High set) 

BLOC I>> 

yellow 

 
Table 5.3: Default settings of blocking functions 

Assignment of the output relays:

 

The relay has five output relays. The fifth output relay is 
provided as permanent alarm relay for self supervision 
is normally on. Output relays 1 - 4 are normally off 
and can be assigned as alarm or tripping relays to the 
current functions which can either be done by using 
the push buttons on the front plate or via serial inter-
face RS485. The assignment of the output relays is 
similar to the setting of parameters, however, only in 
the assignment mode. The assignment mode can be 
reached only via the blocking mode. 
By pressing push button <SELECT/RESET> in blocking 
mode again, the assignment mode is selected. 
 

 
 
 
 
The relays are assigned as follows: LEDs I>, I>>, are 
two-coloured and light up 

green

 when the output re-

lays are assigned as 

alarm relays

 and 

red

 as 

trip-

ping relays

Definition:

 

Alarm relays

 are activated at pickup. 

Tripping relays

 are only activated after elapse of the 

tripping delay. 
After the assignment mode has been activated, first  
LED I> lights up green. Now one or several of the four 
output relays can be assigned to current element I> as 
alarm relays. At the same time the selected alarm re-
lays for frequency element 1 are indicated on the dis-
play. Indication "1_ _ _" means that output relay 1 is 
assigned to this current element. When the display 
shows "_ _ _ _", no alarm relay is assigned to this cur-
rent element. The assignment of output relays 1 - 4 to 
the current elements can be changed by pressing <+> 
and <-> push buttons. The selected assignment can be 
stored by pressing push button <ENTER> and subse-
quent input of the password. By pressing push button 
<SELECT/RESET>, LED I> lights up red. The output re-
lays can now be assigned to this current element as 
tripping relays. 
 
Relays 1 - 4 are selected in the same way as de-
scribed before. By repeatedly pressing of the 
<SELECT/RESET> push button and assignment of the 
relays all elements can be assigned separately to the 
relays. The assignment mode can be terminated at any 
time by pressing the <SELECT/RESET> push button for 
some time (abt. 3 s). 

Note:

 

• 

The function of jumper J2 described in general de-
scription "MR Digital Multifunctional Relays" has no 
function. For relays without assignment mode this 
jumper is used for parameter setting of alarm relays  
(activation at pickup or tripping). 

• 

A form is attached to this description where the set-
ting requested by the customer can be filled-in. This 
form is prepared for telefax transmission and can 
be used for your own reference as well as for tele-
phone queries. 

 

Relay function 

Output relays 

Display- 

Lighted LED 

 

 

1 2 3 4 

indication 

 

I> 

alarm 

 

 

 

_ 2 _ _ 

I>: green 

 

tripping 

 

 

 

1 _ _ _ 

t

I>

: red 

I>> 

alarm 

 

 

 

_ _ 3 _ 

I>>: green 

 

tripping 

 

 

 

1 _ _ _ 

t

I>>

: red 

 

Table 5.4: Example of assignment matrix of the output relay (default settings). 

Summary of Contents for HighTECH Line MRI1IU

Page 1: ...MRI1IU PROTECTION TECHNOLOGY MADE SIMPLE VOLTAGE CONTROLLED TIME OVERCURRENT RELAY HighTECH Line VOLTAGE CONTROLLED TIME OVERCURRENT RELAY Revision A Original document English MANUAL ...

Page 2: ...0 Blocking the protection functions and assignment of the output relays 5 3 Indication of measuring values and fault data 5 3 1 Indication of measuring values 5 3 2 Indication of fault data 5 4 Reset 6 Relay testing and commissioning 6 1 Power On 6 2 Testing the output relays and LEDs 6 3 Checking the set values 6 4 Secondary injection test 6 4 1 Test equipment 6 4 2 Example of test circuit 6 4 3 ...

Page 3: ... high frequence harmonics and DC components induced by faults or system operations Selectable protective functions between definite time overcurrent relay and inverse time overcurrent relay Selectable inverse time characteristics according to BS 142 and IEC 255 4 Normal Inverse Very Inverse Extremely Inverse Reset setting for inverse time characteristics select able High set overcurrent unit with ...

Page 4: ...o output relays with two change over contacts and two with one change over contacts can be assigned as required All relays are working current relays only the relay for self supervision is an idle current relay To prevent that the C B trip coil circuit is interrupted by the MRI1 IU first i e before interruption by the C B auxiliary con tact a dwell time is fixed This setting ensures that the MRI1 ...

Page 5: ...otected object are converted to voltage signals in proportion to the currents via the input trans formers and burden The noise signals caused by in ductive and capacitive coupling are suppressed by an analogue R C filter circuit The analogue voltage signals are fed to the A D converter of the microprocessor and transformed to digital signals through Sample and Hold circuits The analogue signals ar...

Page 6: ... a time overcurrent relay basic unit MRI1 and an additional undervoltage supervision unit The undervoltage supervision unit has an influence on the tripping delay of the overcurrent and short circuit steps by switching two setting points In normal opera tion at nominal voltage the MRI1 IU operates like a normal time overcurrent relay with preselected tripping characteristic IDMT DMT and adjusted p...

Page 7: ...ve parameter SAV ENTER Save parameter SAV ENTER for about 3 s Software version First part e g D01 Sec part e g 8 00 TRIP one time for each part Manual trip TRI TRIP three times Inquire password PSW TRIP ENTER Relay tripped TRIP TRIP or after fault tripping Secret password input XXXX SELECT RESET ENTER System reset SEG SELECT RESET for about 3 s Table 5 1 possible indication messages on the display...

Page 8: ...nyone of these four characteristics can be chosen by using push buttons and can be stored by us ing ENTER push button 5 2 3 Trip delay or time multiplier for phase overcurrent element tI Usually after the characteristic is changed the time delay or the time multiplier should be changed accord ingly In order to avoid an unsuitable arrangement of relay modes due to carelessness of the operator the f...

Page 9: ...D U however flashes red When the current setting for high set element is set out of range on display appears EXIT the high set ele ment of the overcurrent relay is blocked The high set element can be blocked via terminals E8 D8 if the corresponding blocking parameter is set to bloc 5 2 6 Trip delay for high set element tI Independent from the chosen tripping characteristic for I the high set eleme...

Page 10: ... are assigned as alarm relays and red as trip ping relays Definition Alarm relays are activated at pickup Tripping relays are only activated after elapse of the tripping delay After the assignment mode has been activated first LED I lights up green Now one or several of the four output relays can be assigned to current element I as alarm relays At the same time the selected alarm re lays for frequ...

Page 11: ...time when a certain relay function is energised by a fault the corresponding function LED lights up yel low At the same time the phase LED s is are flash ing red to indicate the faulty phase s After the time delay is expired the relay tripps the LED s for faulty phase s indication turn s to a steady red light 5 4 Reset Unit MRI1 IU has the following three possibilities to re set the display of the...

Page 12: ... pressing the push button TRIP twice the display shows the second part of the soft ware version of the relay e g 4 01 The software version should be quoted in all correspondence Press ing the TRIP button once more the display shows PSW Please enter the correct password to proceed with the test The message TRI will follow Confirm this message by pressing the push button TRIP again All output relays...

Page 13: ...cuits terminals A3 A5 A7 and inject a current which is less than the relay pickup current set values in phase 1 terminals B3 B4 and check the measured current on the display by pressing the push button SELECT RESET For a re lay with rated current In 5A for example a secon dary current injection of 1A should be indicated on the display with about 0 2 0 2 x In The voltage will be indicated on the di...

Page 14: ...of inverse time characteristics the injected cur rent should be selected according to the characteristic curve e g two times IS The tripping time may be red from the characteristic curve diagram or calculated with the equations given under technical data Please observe that during the secondary injection test the test current must be very stable not deviating more than 1 Otherwise the test results...

Page 15: ... works and measures correctly 6 6 Maintenance Maintenance testing is generally done on site at regu lar intervals These intervals vary among users depend ing on many factors e g the type of protective relays employed the importance of the primary equipment being protected the user s past experience with the re lay etc For electromechanical or static relays maintenance testing will be performed at ...

Page 16: ...A at IN 5 A 0 1 VA Power consumption in voltage circuit 1 VA Thermal withstand capability in current circuit dynamic current withstand half wave 250 x IN for 1 s 100 x IN for 10 s 30 x IN continuously 4 x IN Thermal withstand in voltage circuit continuously 1 5 x UN 7 2 Common data Dropout to pickup ratio 97 Returning time 30 ms Time lag error class index E 10 ms Minimum operating time 30 ms Trans...

Page 17: ... V 5 from set value 7 3 2 Inverse time overcurrent protection relay According to IEC 255 4 or BS 142 Normal Inverse t I Is t I s 014 0 02 1 Very Inverse t I Is t I s 135 1 Extremely Inverse t I Is t I s 80 2 1 Where t tripping time tI time multiplier I fault current Is Starting current Setting range Step Tolerance ISN ISL tI 0 2 4 0 x IN 0 05 10 0 05 0 1 x IN 0 01 0 02 3 from set value or min 1 In...

Page 18: ... 0 5 0 6 0 8 1 0 1 4 Figure 7 2 Extremely Inverse 1 2 3 4 5 6 7 8 910 20 I IS 0 1 1 10 100 1000 t s tI 10 0 8 0 6 0 4 0 3 0 2 0 0 05 0 1 0 2 0 3 0 4 0 5 0 6 0 8 1 0 1 4 Figure 7 3 Very Inverse 1 10 I IN 0 01 0 1 1 10 100 t s tI I tI 260 0 03 1 0 40 2 0 0 03 I 0 02 4 0 Figure 7 4 Definite time overcurrent relay 7 5 Output contacts Number of relays dependent on relay type Contacts 2 change over cont...

Page 19: ... Default setting Actual setting Default setting Actual setting Default setting Actual setting Plugged no function Not plugged X X Assignment of the output relays Function Relay 1 Relay 2 Relay 3 Relay 4 Default setting Actual setting Default setting Actual setting Default setting Actual setting Default setting Actual setting I alarm X I tripping X I alarm X I tripping X Assignment of the blocking ...

Page 20: ...ow voltage x In 0 2 CHAR I Tripping characteristics DEFT tI Time delay at independent time s 0 03 tI Time multiflier at dependent time characteristics tI Reset Reset Modus for dependent time characteristics I SNormal High set current at nominal voltage x In 1 0 I SLow High set current at low voltage x In 1 0 tI Time delay s 0 03 U Threshold value for undervoltage setting V 10V 20V 40V Rated freque...

Page 21: ...TD_MRI1 IU_05 04_GB 21 ...

Page 22: ... 47884 Kempen Germany Telephone 49 0 21 52 145 1 Internet www SEGelectronics de Sales Telephone 49 0 21 52 145 331 Fax 49 0 21 52 145 354 E mail info SEGelectronics de Service Telephone 49 0 21 52 145 614 Fax 49 0 21 52 145 354 E mail info SEGelectronics de SEG Electronics has company owned plants subsidiaries and branches as well as authorized distributors and other authorized service and sales f...

Reviews: